electricpy.zperlength¶
-
electricpy.zperlength(Rd=
None
, Rself=None
, Rac=None
, Rgwac=None
, De=None
, rho='AVG'
, Ds=None
, Dsgw=None
, dia_gw=None
, Dab=None
, Dbc=None
, Dca=None
, Dagw=None
, Dbgw=None
, Dcgw=None
, resolve=True
, freq=60
)[source]¶ Transmission Line Impedance (RL) Calculator.
Simple impedance matrix generator to provide the full impedance per length matrix.
- Parameters:¶
- Rd : float, optional¶
Resistance Rd term in ohms, will be generated automatically if set to None, default=None
- Rself : float, optional¶
Self Resistance term in ohms.
- Rac : float, optional¶
AC resistance in ohms.
- Rgwac : float, optional¶
Ground-Wire AC resistance in ohms.
- De : float, optional¶
De term, in feet, if None provided, and rho parameter is specified, will interpretively be calculated.
- rho : float, optional¶
Earth resistivity in ohm-meters. default=”AVG”
- Ds : float, optional¶
Distance (self) for each phase conductor in feet, commonly known as GMD.
- Dsgw : float, optional¶
Distance (self) for the ground wire conductor in feet, commonly known as GMD.
- dia_gw : float, optional¶
Ground-Wire diameter in feet, may be used to calculate an approximate Dsgw if no Dsgw is provided.
- Dab : float, optional¶
Distance between phases A and B, in feet.
- Dbc : float, optional¶
Distance between phases B and C, in feet.
- Dca : float, optional¶
Distance between phases C and A, in feet.
- Dagw : float, optional¶
Distance between phase A and ground conductor, in feet.
- Dbgw : float, optional¶
Distance between phase B and ground conductor, in feet.
- Dcgw : float, optional¶
Distance between phase C and ground conductor, in feet.
- resolve : bool, optional¶
Control argument to specify whether the resultant ground-wire inclusive per-length impedance matrix should be reduced to a 3x3 equivalent matrix. default=True
- freq : float, optional¶
System frequency in Hertz.