Source code for electricpy.fault

################################################################################
"""
Electrical Power Engineering Faults Calculations.

>>> from electricpy import fault
"""
################################################################################

import numpy as _np
import matplotlib.pyplot as _plt
from scipy.optimize import fsolve as _fsolve

from electricpy.constants import *
from electricpy.conversions import seq_to_abc


def _phaseroll(M012, reference):
    # Compute Dot Product
    return seq_to_abc(M012, reference)


# Define Single Line to Ground Fault Function
[docs] def single_phase_to_ground_fault(Vth, Zseq, Rf=0, sequence=True, reference='A'): r""" Single-Phase-to-Ground Fault Calculator. This function will evaluate the Zero, Positive, and Negative sequence currents for a single-line-to-ground fault. .. math:: I_1 = \frac{V_{th}}{Z_0+Z_1+Z_2+3*R_f} .. math:: I_2 = I_1 .. math:: I_0 = I_1 Parameters ---------- Vth: complex The Thevenin-Equivalent-Voltage Zseq: list of complex Tupple of sequence reactances as (Z0, Z1, Z2) Rf: complex, optional The fault resistance, default=0 sequence: bool, optional Control argument to force return into symmetrical- or phase-domain values. reference: {'A', 'B', 'C'} Single character denoting the reference, default='A' Returns ------- Ifault: list of complex, The Array of Fault Currents as (If0, If1, If2) """ # Decompose Reactance Tuple X0, X1, X2 = Zseq # Ensure that X-components are imaginary if not isinstance(X0, complex): X0 *= 1j if not isinstance(X1, complex): X1 *= 1j if not isinstance(X2, complex): X2 *= 1j # Calculate Fault Current Ifault = Vth / (X0 + X1 + X2 + 3 * Rf) Ifault = _np.array([Ifault, Ifault, Ifault]) # Prepare Value for return if not sequence: Ifault = _phaseroll(Ifault, reference) # Convert to ABC-Domain # Return Value return Ifault
# Alias Original Name phs1g = single_phase_to_ground_fault # Define Double Line to Ground Fault Current Calculator
[docs] def double_phase_to_ground_fault(Vth, Zseq, Rf=0, sequence=True, reference='A'): r""" Double-Line-to-Ground Fault Calculator. This function will evaluate the Zero, Positive, and Negative sequence currents for a double-line-to-ground fault. .. math:: I_1 = \frac{V_{th}}{Z_1+\frac{Z_2*(Z_0+3*R_f)}{Z_0+Z_2+3*R_f}} .. math:: I_2 = -\frac{V_{th}-Z_1*I_1}{X_2} .. math:: I_0 = -\frac{V_{th}-Z_1*I_1}{X_0+3*R_f} Parameters ---------- Vth: complex The Thevenin-Equivalent-Voltage Zseq: list of complex Tupple of sequence reactances as (Z0, Z1, Z2) Rf: complex, optional The fault resistance, default=0 sequence: bool, optional Control argument to force return into symmetrical- or phase-domain values. reference: {'A', 'B', 'C'} Single character denoting the reference, default='A' Returns ------- Ifault: list of complex, The Array of Fault Currents as (If0, If1, If2) """ # Decompose Reactance Tuple X0, X1, X2 = Zseq # Ensure that X-components are imaginary if not isinstance(X0, complex): X0 *= 1j if not isinstance(X1, complex): X1 *= 1j if not isinstance(X2, complex): X2 *= 1j # Calculate Fault Currents If1 = Vth / (X1 + (X2 * (X0 + 3 * Rf)) / (X0 + X2 + 3 * Rf)) If2 = -(Vth - X1 * If1) / X2 If0 = -(Vth - X1 * If1) / (X0 + 3 * Rf) Ifault = _np.array([If0, If1, If2]) # Return Currents if not sequence: Ifault = _phaseroll(Ifault, reference) # Convert to ABC-Domain return Ifault
# Alias Original Name phs2g = double_phase_to_ground_fault # Define Phase-to-Phase Fault Current Calculator
[docs] def phase_to_phase_fault(Vth, Zseq, Rf=0, sequence=True, reference='A'): r""" Line-to-Line Fault Calculator. This function will evaluate the Zero, Positive, and Negative sequence currents for a phase-to-phase fault. .. math:: I_1 = \frac{V_{th}}{Z_1+Z_2+R_f} .. math:: I_2 = -I_1 .. math:: I_0 = 0 Parameters ---------- Vth: complex The Thevenin-Equivalent-Voltage Zseq: list of complex Tupple of sequence reactances as (Z0, Z1, Z2) Rf: complex, optional The fault resistance, default=0 sequence: bool, optional Control argument to force return into symmetrical- or phase-domain values. reference: {'A', 'B', 'C'} Single character denoting the reference, default='A' Returns ------- Ifault: list of complex, The Array of Fault Currents as (If0, If1, If2) """ # Decompose Reactance Tuple X0, X1, X2 = Zseq # Ensure that X-components are imaginary if not isinstance(X0, complex): X0 *= 1j if not isinstance(X1, complex): X1 *= 1j if not isinstance(X2, complex): X2 *= 1j # Calculate Fault Currents If0 = 0 If1 = Vth / (X1 + X2 + Rf) If2 = -If1 Ifault = _np.array([If0, If1, If2]) # Return Currents if not sequence: Ifault = _phaseroll(Ifault, reference) # Convert to ABC-Domain return Ifault
# Alias Original Name phs2 = phase_to_phase_fault # Define Three-Phase Fault Current Calculator
[docs] def three_phase_fault(Vth, Zseq, Rf=0, sequence=True, reference='A'): r""" Three-Phase Fault Calculator. This function will evaluate the Zero, Positive, and Negative sequence currents for a three-phase fault. .. math:: I_1 = \frac{V_{th}}{Z_1+R_1} .. math:: I_2 = 0 .. math:: I_0 = 0 Parameters ---------- Vth: complex The Thevenin-Equivalent-Voltage Zseq: list of complex Tupple of sequence reactances as (Z0, Z1, Z2) Rf: complex, optional The fault resistance, default=0 sequence: bool, optional Control argument to force return into symmetrical- or phase-domain values. reference: {'A', 'B', 'C'} Single character denoting the reference, default='A' Returns ------- Ifault: list of complex The Fault Current, equal for 0, pos., and neg. seq. """ # Decompose Reactance Tuple X0, X1, X2 = Zseq # Ensure that X-components are imaginary if not isinstance(X1, complex): X1 *= 1j # Calculate Fault Currents Ifault = Vth / (X1 + Rf) Ifault = _np.array([0, Ifault, 0]) # Prepare to Return Value if not sequence: Ifault = _phaseroll(Ifault, reference) # Convert to ABC-Domain return Ifault
# Alias Original Name phs3 = three_phase_fault # Define Single Pole Open Calculator
[docs] def poleopen1(Vth, Zseq, sequence=True, reference='A'): r""" Single Pole Open Fault Calculator. This function will evaluate the Zero, Positive, and Negative sequence currents for a single pole open fault. .. math:: I_1 = \frac{V_{th}}{Z_1+(\frac{1}{Z_2}+\frac{1}{Z_0})^-1} .. math:: I_2 = -I_1 * \frac{Z_0}{Z_2+Z_0} .. math:: I_0 = -I_1 * \frac{Z_2}{Z_2+Z_0} Parameters ---------- Vth: complex The Thevenin-Equivalent-Voltage Zseq: list of complex Tupple of sequence reactances as (Z0, Z1, Z2) sequence: bool, optional Control argument to force return into symmetrical- or phase-domain values. reference: {'A', 'B', 'C'} Single character denoting the reference, or the faulted phase indicator; default='A' Returns ------- Ifault: list of complex, The Array of Fault Currents as (If0, If1, If2) """ # Decompose Reactance Tuple X0, X1, X2 = Zseq # Ensure that X-components are imaginary if not isinstance(X0, complex): X0 *= 1j if not isinstance(X1, complex): X1 *= 1j if not isinstance(X2, complex): X2 *= 1j # Calculate Fault Currents If1 = Vth / (X1 + (1 / X2 + 1 / X0) ** (-1)) If2 = -If1 * X0 / (X2 + X0) If0 = -If1 * X2 / (X2 + X0) Ifault = _np.array([If0, If1, If2]) # Return Currents if not sequence: Ifault = _phaseroll(Ifault, reference) # Convert to ABC-Domain return Ifault
# Define Double Pole Open Calculator
[docs] def poleopen2(Vth, Zseq, sequence=True, reference='A'): r""" Single Pole Open Fault Calculator. This function will evaluate the Zero, Positive, and Negative sequence currents for a single pole open fault. .. math:: I_1 = \frac{V_{th}}{Z_1+Z_2+Z_0} .. math:: I_2 = I_1 .. math:: I_0 = I_1 Parameters ---------- Vth: complex The Thevenin-Equivalent-Voltage Zseq: list of complex Tupple of sequence reactances as (Z0, Z1, Z2) sequence: bool, optional Control argument to force return into symmetrical- or phase-domain values. reference: {'A', 'B', 'C'} Single character denoting the reference, or the faulted phase indicator; default='A' Returns ------- Ifault: list of complex, The Array of Fault Currents as (If0, If1, If2) """ # Decompose Reactance Tuple X0, X1, X2 = Zseq # Ensure that X-components are imaginary if not isinstance(X0, complex): X0 *= 1j if not isinstance(X1, complex): X1 *= 1j if not isinstance(X2, complex): X2 *= 1j # Calculate Fault Currents If1 = Vth / (X1 + X2 + X0) If2 = If1 If0 = If1 Ifault = _np.array([If0, If1, If2]) # Return Currents if not sequence: Ifault = _phaseroll(Ifault, reference) # Convert to ABC-Domain return Ifault
# Define MVA Short Circuit
[docs] def short_circuit_mva(Zth=None, Isc=None, Vth=1): r""" Short-Circuit MVA Calculator. Function defines a method of interpretively calculating the short-circuit MVA value given two of the three arguments. The formulas are all based around the following: .. math:: MVA_{sc} = V_{th}*I_{sc} .. math:: V_{th} = I_{sc}*Z_{th} Parameters ---------- Zth: float The Thevenin-Equivalent-Impedance Isc: float, optional Short-Circuit-Current, if left as None, will force function to use default setting for Vth. default=None Vth: float, optional The Thevenin-Equivalent-Voltage, defaults to a 1-per-unit value. default=1 Returns ------- MVA: float Short-Circuit MVA, not described as three-phase or otherwise, such determination is dependent upon inputs. """ # Test for too few inputs if not any((Zth, Isc)): raise ValueError("Either Zth or Isc must be specified.") # Condition Inputs if Zth is not None: Zth = abs(Zth) if Isc is not None: Isc = abs(Isc) if Vth != 1: Vth = abs(Vth) # Calculate MVA from one of the available methods if all((Zth, Isc)): MVA = Isc ** 2 * Zth elif all((Zth, Vth)): MVA = Vth ** 2 / Zth else: MVA = Vth * Isc # Return Value return MVA
# Alias Original Name scMVA = short_circuit_mva # Define Explicitly 3-Phase MVAsc Calculator
[docs] def phs3mvasc(Vth, Zseq, Rf=0, Sbase=1): r""" Three-Phase MVA Short-Circuit Calculator. Calculator to evaluate the Short-Circuit MVA of a three-phase fault given the system parameters of Vth, Zseq, and an optional Rf. Uses the formula as follows: .. math:: MVA_{sc} = \frac{\left|V_{th}^2\right|}{|Z_1|} * Sbase Parameters ---------- Vth: complex The Thevenin-Equivalent-Voltage Zseq: list of complex Tupple of sequence reactances as (Z0, Z1, Z2) Rf: complex, optional The fault resistance, default=0 Sbase: real, optional The per-unit base for power. default=1 Returns ------- MVA: real Three-Phase Short-Circuit MVA. """ # Calculate Three-Phase MVA MVA = abs(Vth) ** 2 / abs(Zseq[1]) * Sbase # Scale VA to MVA if Sbase is not 1 if Sbase != 1: MVA = MVA * 1e-6 # Divide by 1e6 (M) # Return return MVA
# Define Explicitly 1-Phase MVAsc Calculator
[docs] def phs1mvasc(Vth, Zseq, Rf=0, Sbase=1): r""" Single-Phase MVA Short-Circuit Calculator. Calculator to evaluate the Short-Circuit MVA of a single-phase fault given the system parameters of Vth, Zseq, and an optional Rf. Uses the formula as follows: .. math:: MVA_{sc} = \left|I_1^2\right|*|Z_1| * Sbase where: .. math:: I_1 = \frac{V_{th}}{Z_0+Z_1+Z_2+3*R_f} Parameters ---------- Vth: complex The Thevenin-Equivalent-Voltage Zseq: list of complex Tupple of sequence reactances as (Z0, Z1, Z2) Rf: complex, optional The fault resistance, default=0 Sbase: real, optional The per-unit base for power. default=1 Returns ------- MVA: real Single-Phase Short-Circuit MVA. """ # Decompose Reactance Tuple X0, X1, X2 = Zseq # Ensure that X-components are imaginary if not isinstance(X0, complex): X0 *= 1j if not isinstance(X1, complex): X1 *= 1j if not isinstance(X2, complex): X2 *= 1j # Calculate Fault Current Ifault = Vth / (X0 + X1 + X2 + 3 * Rf) # Calculate MVA MVA = abs(Ifault) ** 2 * abs(X1) * Sbase # Scale VA to MVA if Sbase is not 1 if Sbase != 1: MVA = MVA * 1e-6 # Divide by 1e6 (M) # Return return MVA
# Define Faulted Bus Voltage Calculator
[docs] def busvolt(k, n, Vpf, Z0, Z1, Z2, If, sequence=True, reference='A'): """ Faulted Bus Voltage Calculator. This function is designed to calculate the bus voltage(s) given a specific set of fault characteristics. Parameters ---------- k: float Bus index at which to calculate faulted voltage n: float Bus index at which fault occurred Vpf: complex Voltage Pre-Fault, Singular Number Z0: ndarray Zero-Sequence Impedance Matrix Z1: ndarray Positive-Sequence Impedance Matrix Z2: ndarray Negative-Sequence Impedance Matrix If: complex Sequence Fault Current Evaluated at Bus *n* sequence: bool, optional Control argument to force return into symmetrical- or phase-domain values. reference: {'A', 'B', 'C'} Single character denoting the reference, default='A' Returns ------- Vf: complex The Fault Voltage, set of sequence or phase voltages as specified by *sequence* """ # Condition Inputs k = k - 1 n = n - 1 Z0 = _np.asarray(Z0) Z1 = _np.asarray(Z1) Z2 = _np.asarray(Z2) If = _np.asarray(If) # Generate Arrays For Calculation Vfmat = _np.array([0, Vpf, 0]).T Zmat = _np.array([[Z0[k, n], 0, 0], [0, Z1[k, n], 0], [0, 0, Z2[k, n]]]) # Perform Calculation Vf = Vfmat - Zmat.dot(If) if not sequence: Vf = _phaseroll(Vf, reference) # Convert to ABC-Domain return Vf
# Define CT Saturation Function
[docs] def ct_saturation(XoR, Imag, Vrated, Irated, CTR, Rb, Xb, remnance=0, freq=60, ALF=20): r""" Electrical Current Transformer Saturation Calculator. A function to determine the saturation value and a boolean indicator showing whether or not CT is -in fact- saturated. To perform this evaluation, we must satisfy the equation: .. math:: 20\geq(1+\frac{X}{R})*\frac{|I_{mag}|}{I_{rated}*CTR} *\frac{\left|R_{burden}+j*\omega*\frac{X_{burden}} {\omega}\right|*100}{V_{rated}*(1-remnanc)} Parameters ---------- XoR: float The X-over-R ratio of the system. Imag: float The (maximum) current magnitude to use for calculation, typically the fault current. Vrated: float The rated voltage (accompanying the C-Class value) of the CT. Irated: float The rated secondary current for the CT. CTR: float The CT Ratio (primary/secondary, N) to be used. Rb: float The total burden resistance in ohms. Xb: float The total burden reactance in ohms. remnance: float, optional The system flux remnance, default=0. freq: float, optional The system frequency in Hz, default=60. ALF: float, optional The Saturation Constant which must be satisfied, default=20. Returns ------- result: float The calculated Saturation value. saturation: bool Boolean indicator to mark presence of saturation. """ # Define omega w = 2 * _np.pi * freq # Find Lb Lb = Xb / w # Re-evaluate Vrated Vrated = Vrated * (1 - remnance) # Calculate each "term" (multiple) t1 = (1 + XoR) t2 = (Imag / (Irated * CTR)) t3 = abs(Rb + 1j * w * Lb) * 100 / Vrated # Evaluate result = t1 * t2 * t3 # Test for saturation saturation = result >= ALF # Return Results return result, saturation
# Define C-Class Calculator
[docs] def ct_cclass(XoR, Imag, Irated, CTR, Rb, Xb, remnance=0, sat_crit=20): r""" Electrical Current Transformer (CT) C-Class Function. A function to determine the C-Class rated voltage for a CT. The formula shown below demonstrates the standard formula which is normally used to evaluate the saturation criteria. Worth noting here, is the fact that :math:`V_{rated}` is the CT C-Class. .. math:: \text{Saturation Criteria}=\frac{(1+\frac{X}{R})\cdot \frac{|I_{mag}|}{I_{rated}\cdot CTR}\cdot\frac{\left| R_{burden}+j\cdot X_{burden}\right|\cdot100}{V_{rated}}} {1-remnance} For the purposes of this function, the above formula is applied as follows to evaluate the CT C-Class such as to satisfy the saturation criteria defined. .. math:: \text{CT C-Class}=\frac{(1+\frac{X}{R})\cdot \frac{|I_{mag}|}{I_{rated}\cdot CTR}\cdot\frac{ \left|R_{burden}+j\cdot X_{burden}\right|\cdot100} {\text{Saturation Criteria (i.e., 20)}}}{1-remnance} Parameters ---------- XoR: float The X-over-R ratio of the system. Imag: float The (maximum) current magnitude to use for calculation, typically the fault current. Irated: float The rated secondary current for the CT. CTR: float The CT Ratio (primary/secondary, N) to be used. Rb: float The total burden resistance in ohms. Xb: float The total burden reactance in ohms. remnance: float, optional The system flux remnance, default=0. sat_crit: float, optional The saturation criteria which must be satisfied, typically such that CT saturation will not occur, default=20. Returns ------- c_class: float The calculated C-Class rated voltage. """ # Calculate each "term" (multiple) t1 = (1 + XoR) t2 = (Imag / (Irated * CTR)) t3 = abs(Rb + 1j * Xb) * 100 / sat_crit # Evaluate Vr_w_rem = t1 * t2 * t3 c_class = Vr_w_rem / (1 - remnance) # Return Result return c_class
# Define Saturation Voltage at Rated Burden
[docs] def ct_satratburden(Inom, VArat=None, ANSIv=None, ALF=20, ): r""" Electrical Current Transformer (CT) Saturation at Rated Burden Calculator. A function to determine the Saturation at rated burden. .. math:: V_{saturated}=ALF*\frac{VA_{rated}}{I_{nominal}} where: .. math:: VA_{rated}=I_{nominal}*\frac{ANSI_{voltage}}{20} Parameters ---------- Inom: float Nominal Current VArat: float, optional, exclusive The apparent power (VA) rating of the CT. ANSIv: float, optional, exclusive The ANSI voltage requirement to meet. ALF: float, optional Accuracy Limit Factor, default=20. Returns ------- Vsat: float The saturated voltage. """ # Validate Inputs if VArat is None and ANSIv is None: raise ValueError("VArat or ANSIv must be specified.") elif VArat is None: # Calculate VArat from ANSIv VArat = Inom * ANSIv / (20) # Determine Vsaturation Vsat = ALF * VArat / Inom return Vsat
# Define CT Vpeak Formula
[docs] def ct_vpeak(Zb, Ip, CTR): r""" Electrical Current Transformer (CT) Peak Voltage Calculator. Simple formula to calculate the Peak Voltage of a CT. .. math:: \sqrt{3.5*|Z_burden|*I_{peak}*CTR} Parameters ---------- Zb: float The burden impedance magnitude (in ohms). Ip: float The peak current for the CT. CTR: float The CTR turns ratio of the CT. Returns ------- Vpeak: float The peak voltage. """ return _np.sqrt(3.5 * abs(Zb) * Ip * CTR)
# Define Saturation Time Calculator
[docs] def ct_timetosat(Vknee, XoR, Rb, CTR, Imax, ts=None, npts=100, freq=60, plot=False): r""" Electrical Current Transformer (CT) Time to Saturation Function. Function to determine the "time to saturate" for an underrated C-Class CT using three standard curves described by Juergen Holbach. Parameters ---------- Vknee: float The knee-voltage for the CT. XoR: float The X-over-R ratio of the system. Rb: float The total burden resistance in ohms. CTR: float The CT Ratio (primary/secondary, N) to be used. Imax: float The (maximum) current magnitude to use for calculation, typically the fault current. ts: numpy.ndarray or float, optional The time-array or particular (floatint point) time at which to calculate the values. default=_np.linspace(0,0.1,freq*npts) npts: float, optional The number of points (per cycle) to calculate if ts is not specified, default=100. freq: float, optional The system frequency in Hz, default=60. plot: bool, optional Control argument to enable plotting of calculated curves, default=False. """ # Calculate omega w = 2 * _np.pi * freq # Calculate Tp Tp = XoR / w # If ts isn't specified, generate it if ts is None: ts = _np.linspace(0, 0.1, freq * npts) # Calculate inner term term = -XoR * (_np.exp(-ts / Tp) - 1) # Calculate Vsaturation terms Vsat1 = Imax * Rb * (term + 1) Vsat2 = Imax * Rb * (term - _np.sin(w * ts)) Vsat3 = Imax * Rb * (1 - _np.cos(w * ts)) # If plotting requested if plot and isinstance(ts, _np.ndarray): _plt.plot(ts, Vsat1, label="Vsat1") _plt.plot(ts, Vsat2, label="Vsat2") _plt.plot(ts, Vsat3, label="Vsat3") _plt.axhline(Vknee, label="V-knee", linestyle='--') _plt.title("Saturation Curves") _plt.xlabel("Time (ts)") _plt.legend() _plt.show() elif plot: print("Unable to plot a single point, *ts* must be a numpy-array.") # Determine the crossover points for each saturation curve Vsat1c = Vsat2c = Vsat3c = 0 if isinstance(ts, _np.ndarray): for i in range(len(ts)): if Vsat1[i] > Vknee and Vsat1c == 0: Vsat1c = ts[i - 1] if Vsat2[i] > Vknee and Vsat2c == 0: Vsat2c = ts[i - 1] if Vsat3[i] > Vknee and Vsat3c == 0: Vsat3c = ts[i - 1] results = (Vsat1c, Vsat2c, Vsat3c) else: results = (Vsat1, Vsat2, Vsat3) return results
# Define Function to Calculate TRV
[docs] def pktransrecvolt(C, L, R=0, VLL=None, VLN=None, freq=60): """ Peak Transient Recovery Function. Peak Transient Recovery Voltage calculation function, evaluates the peak transient recovery voltage (restriking voltage) and the Rate-of-Rise-Recovery Voltage. Parameters ---------- C: float Capacitance Value in Farads. L: float Inductance in Henries. R: float, optional The resistance of the system used for calculation, default=0. VLL: float, exclusive Line-to-Line voltage, exclusive optional argument. VLN: float, exclusive Line-to-Neutral voltage, exclusive optional argument. freq: float, optional System frequency in Hz. Returns ------- Vcpk: float Peak Transient Recovery Voltage in volts. RRRV: float The RRRV (Rate-of-Rise-Recovery Voltage) calculated given the parameters in volts per second. """ # Evaluate alpha, omega-n, and fn alpha = R / (2 * L) wn = 1 / _np.sqrt(L * C) - alpha fn = wn / (2 * _np.pi) # Evaluate Vm if VLL is not None: Vm = _np.sqrt(2 / 3) * VLL elif VLN is not None: Vm = _np.sqrt(2) * VLN else: raise ValueError("One voltage must be specified.") # Evaluate Vcpk (worst case) Vcpk = wn ** 2 / (wn ** 2 - 2 * _np.pi * freq) * Vm * 2 # Evaluate RRRV RRRV = 2 * Vm * fn / 0.5 return Vcpk, RRRV
# Define TRV Reduction Resistor Function
[docs] def trvresistor(C, L, reduction, Rd0=500, wd0=260e3, tpk0=10e-6): """ Transient Recovery Voltage (TRV) Reduction Resistor Function. Function to find the resistor value that will reduce the TRV by a specified percentage. Parameters ---------- C: float Capacitance Value in Farads. L: float Inductance in Henries. reduction: float The percentage that the TRV should be reduced by. Rd0: float, optional Damping Resistor Evaluation Starting Point, default=500 wd0: float, optional Omega-d evaluation starting point, default=260*k tpk0: float, optional Time of peak voltage evaluation starting point, default=10*u Returns ------- Rd: float Damping resistor value, in ohms. wd: float Omega-d tpk: float Time of peak voltage. """ # Evaluate omega-n wn = 1 / _np.sqrt(L * C) # Generate Constant Factor fctr = (1 - reduction) * 2 - 1 # Define Function Set def equations(data): Rd, wd, tpk = data X = _np.sqrt(wn ** 2 - (1 / (2 * Rd * C)) ** 2) - wd Y = _np.exp(-tpk / (2 * Rd * C)) - fctr Z = wd * tpk - _np.pi return (X, Y, Z) Rd, wd, tpk = _fsolve(equations, (Rd0, wd0, tpk0)) return Rd, wd, tpk
# Define Time-Overcurrent Trip Time Function
[docs] def toctriptime(I, Ipickup, TD, curve="U1", CTR=1): """ Time OverCurrent Trip Time Function. Time-OverCurrent Trip Time Calculator, evaluates the time to trip for a specific TOC (51) element given the curve type, current characteristics and time-dial setting. Parameters ---------- I: float Measured Current in Amps Ipickup: float Fault Current Pickup Setting (in Amps) TD: float Time Dial Setting curve: string, optional Name of specified TOC curve, may be entry from set: {U1,U2,U3,U4,U5,C1,C2,C3,C4,C5}, default=U1 CTR: float, optional Current Transformer Ratio, default=1 Returns ------- tt: float Time-to-Trip for characterized element. """ # Condition Inputs curve = curve.upper() # Define Dictionary of Constants const = {"U1": {"A": 0.0104, "B": 0.2256, "P": 0.02}, "U2": {"A": 5.95, "B": 0.180, "P": 2.00}, "U3": {"A": 3.88, "B": 0.0963, "P": 2.00}, "U4": {"A": 5.67, "B": 0.352, "P": 2.00}, "U5": {"A": 0.00342, "B": 0.00262, "P": 0.02}, "C1": {"A": 0.14, "B": 0, "P": 0.02}, "C2": {"A": 13.5, "B": 0, "P": 2.00}, "C3": {"A": 80.0, "B": 0, "P": 2.00}, "C4": {"A": 120.0, "B": 0, "P": 2.00}, "C5": {"A": 0.05, "B": 0, "P": 0.04}} # Load Constants A = const[curve]["A"] B = const[curve]["B"] P = const[curve]["P"] # Evaluate M M = I / (CTR * Ipickup) # Evaluate Trip Time tt = TD * (A / (M ** P - 1) + B) return tt
# Define Time Overcurrent Reset Time Function
[docs] def tocreset(I, Ipickup, TD, curve="U1", CTR=1): """ Time OverCurrent Reset Time Function. Function to calculate the time to reset for a TOC (Time-OverCurrent, 51) element. Parameters ---------- I: float Measured Current in Amps Ipickup: float Fault Current Pickup Setting (in Amps) TD: float Time Dial Setting curve: string, optional Name of specified TOC curve, may be entry from set: {U1,U2,U3,U4,U5,C1,C2,C3,C4,C5}, default=U1 CTR: float, optional Current Transformer Ratio, default=1 Returns ------- tr: float Time-to-Reset for characterized element. """ # Condition Inputs curve = curve.upper() # Define Dictionary of Constants C = {"U1": 1.08, "U2": 5.95, "U3": 3.88, "U4": 5.67, "U5": 0.323, "C1": 13.5, "C2": 47.3, "C3": 80.0, "C4": 120.0, "C5": 4.85} # Evaluate M M = I / (CTR * Ipickup) # Evaluate Reset Time tr = TD * (C[curve] / (1 - M ** 2)) return tr
# Define Pickup Current Calculation
[docs] def pickup(Iloadmax, Ifaultmin, scale=0, printout=False, units="A"): """ Electrical Current Pickup Selection Assistant. Used to assist in evaluating an optimal phase-over-current pickup setting. Uses maximum load and minimum fault current to provide user assistance. Parameters ---------- Iloadmax: float The maximum load current in amps. Ifaultmin: float The minimum fault current in amps. scale: int, optional Control scaling to set number of significant figures. default=0 printout: boolean, optional Control argument to enable printing of intermediate stages, default=False. units: string, optional String to be appended to any printed output denoting the units of which are being printed, default="A" Returns ------- setpoint: float The evaluated setpoint at which the function suggests the phase-over-current pickup setting be placed. """ IL2 = 2 * Iloadmax IF2 = Ifaultmin / 2 exponent = len(str(IL2).split('.')[0]) setpoint = _np.ceil(IL2 * 10 ** (-exponent + 1 + scale)) * 10 ** (exponent - 1 - scale) if printout: print("Range Min:", IL2, units, "\t\tRange Max:", IF2, units) if IF2 < setpoint: setpoint = IL2 if IL2 > IF2: raise ValueError("Invalid Parameters.") if printout: print("Current Pickup:", setpoint, units) return setpoint
# Define Time-Dial Coordination Function
[docs] def tdradial(I, CTI, Ipu_up, Ipu_dn=0, TDdn=0, curve="U1", scale=2, freq=60, CTR_up=1, CTR_dn=1, tfixed=None): """ Radial Time Dial Coordination Function. Function to evaluate the Time-Dial (TD) setting in radial schemes where the Coordinating Time Interval (CTI) and the up/downstream pickup settings are known along with the TD setting for the downstream protection. Parameters ---------- I: float Measured fault current in Amps, typically set using the maximum fault current available. CTI: float Coordinating Time Interval in cycles. Ipu_up: float Pickup setting for upstream protection, specified in amps Ipu_dn: float, optional Pickup setting for downstream protection, specified in amps, default=0 TDdn: float, optional Time-Dial setting for downstream protection, specified in seconds, default=0 curve: string, optional Name of specified TOC curve, may be entry from set: {U1,U2,U3,U4,U5,C1,C2,C3,C4,C5}, default=U1 scale: int, optional Scaling value used to evaluate a practical TD setting, default=2 freq: float, optional System operating frequency, default=60 CTR_up: float, optional Current Transformer Ratio for upstream relay. default=1 CTR_dn: float, optional Current Transformer Ratio for downstream relay. default=1 tfixed: float, optional Used to specify a fixed time delay for coordinated protection elements, primarily used for coordinating TOC elements (51) with OC elements (50) with a fixed tripping time. Overrides downstream TOC arguments including *Ipu_dn* and *TDdn*. Returns ------- TD: float Calculated Time-Dial setting according to radial scheme logical analysis. """ # Condition Inputs curve = curve.upper() # Define Dictionary of Constants const = {"U1": {"A": 0.0104, "B": 0.2256, "P": 0.02}, "U2": {"A": 5.95, "B": 0.180, "P": 2.00}, "U3": {"A": 3.88, "B": 0.0963, "P": 2.00}, "U4": {"A": 5.67, "B": 0.352, "P": 2.00}, "U5": {"A": 0.00342, "B": 0.00262, "P": 0.02}, "C1": {"A": 0.14, "B": 0, "P": 0.02}, "C2": {"A": 13.5, "B": 0, "P": 2.00}, "C3": {"A": 80.0, "B": 0, "P": 2.00}, "C4": {"A": 120.0, "B": 0, "P": 2.00}, "C5": {"A": 0.05, "B": 0, "P": 0.04}} # Load Constants A = const[curve]["A"] B = const[curve]["B"] P = const[curve]["P"] if tfixed is None: # Evaluate in seconds from cycles CTI = CTI / freq # Evaluate M M = I / (CTR_dn * Ipu_dn) # Evaluate Trip Time tpu_desired = TDdn * (A / (M ** P - 1) + B) + CTI else: tpu_desired = tfixed + CTI # Re-Evaluate M M = I / (CTR_up * Ipu_up) # Calculate TD setting TD = tpu_desired / (A / (M ** 2 - 1) + B) # Scale and Round TD = _np.floor(TD * 10 ** scale) / 10 ** scale return TD
# Define TAP Calculator
[docs] def protectiontap(S, CTR=1, VLN=None, VLL=None): """ Protection TAP Setting Calculator. Evaluates the required TAP setting based on the rated power of a transformer (the object being protected) and the voltage (either primary or secondary) in conjunction with the CTR (current transformer ratio) for the side in question (primary/ secondary). Parameters ---------- CTR: float The Current Transformer Ratio. S: float Rated apparent power magnitude (VA/VAR/W). VLN: float, exclusive Line-to-Neutral voltage in volts. VLL: float, exclusive Line-to-Line voltage in volts. Returns ------- TAP: float The TAP setting required to meet the specifications. """ # Condition Voltage(s) if VLL is not None: V = abs(_np.sqrt(3) * VLL) elif VLN is not None: V = abs(3 * VLN) else: raise ValueError("One or more voltages must be provided.") # Calculate TAP TAP = abs(S) / (V * CTR) return TAP
# Define Current Correction Calculator
[docs] def correctedcurrents(Ipri, TAP, correction="Y", CTR=1): """ Electrical Transformer Current Correction Function. Function to evaluate the currents as corrected for microprocessor- based relay protection schemes. Parameters ---------- Ipri: list of complex Three-phase set (IA, IB, IC) of primary currents. TAP: float Relay's TAP setting. correction: string, optional String defining correction factor, may be one of: (Y, D+, D-, Z); Y denotes Y (Y0) connection, D+ denotes Dab (D1) connection, D- denotes Dac (D11) connection, and Z (Z12) denotes zero-sequence removal. default="Y" CTR: float Current Transformer Ratio, default=1 Returns ------- Isec_corr: list of complex The corrected currents to perform operate/restraint calculations with. """ # Define Matrix Lookup MAT = {"Y": XFMY0, "D+": XFMD1, "D-": XFMD11, "Z": XFM12} # Condition Inputs Ipri = _np.asarray(Ipri) if isinstance(correction, list): mult = MAT[correction[0]] for i in correction[1:]: mult = mult.dot(MAT[i]) elif isinstance(correction, str): mult = MAT[correction] elif isinstance(correction, _np.ndarray): mult = correction else: raise ValueError("Correction must be string or list of strings.") # Evaluate Corrected Current Isec_corr = 1 / TAP * mult.dot(Ipri / CTR) return Isec_corr
# Define Iop/Irt Calculator
[docs] def iopirt(IpriHV, IpriLV, TAPHV, TAPLV, corrHV="Y", corrLV="Y", CTRHV=1, CTRLV=1): """ Operate/Restraint Current Calculator. Calculates the operating current (Iop) and the restraint current (Irt) as well as the slope. Parameters ---------- IpriHV: list of complex Three-phase set (IA, IB, IC) of primary currents on the high-voltage side of power transformer. IpriLV list of complex Three-phase set (IA, IB, IC) of primary currents on the low-voltage side of power transformer. TAPHV float Relay's TAP setting for high-voltage side of power transformer. TAPLV float Relay's TAP setting for low-voltage side of power transformer. corrHV string, optional String defining correction factor on high-voltage side of power transformer, may be one of: (Y, D+, D-, Z); Y denotes Y (Y0) connection, D+ denotes Dab (D1) connection, D- denotes Dac (D11) connection, and Z (Z12) denotes zero-sequence removal. default="Y" corrLV string, optional String defining correction factor on low-voltage side of power transformer, may be one of: (Y, D+, D-, Z); Y denotes Y (Y0) connection, D+ denotes Dab (D1) connection, D- denotes Dac (D11) connection, and Z (Z12) denotes zero-sequence removal. default="Y" CTRHV float Current Transformer Ratio for high-voltage side of power transformer, default=1 CTRLV float Current Transformer Ratio for low-voltage side of power transformer, default=1 Returns ------- Iop: list of float The operating currents for phases A, B, and C. Irt: list of float The restraint currents for phases A, B, and C. slope: list of float The calculated slopes for phases A, B, and C. """ # Calculate Corrected Currents IcorHV = correctedcurrents(IpriHV, TAPHV, corrHV, CTRHV) IcorLV = correctedcurrents(IpriLV, TAPLV, corrLV, CTRLV) # Calculate Operate/Restraint Currents Iop = _np.absolute(IcorHV + IcorLV) Irt = _np.absolute(IcorHV) + _np.absolute(IcorLV) # Calculate Slopes slope = Iop / Irt return Iop, Irt, slope
# Define Symmetrical/RMS Current Calculation
[docs] def symrmsfaultcur(V, R, X, t=1 / 60, freq=60): """ Symmetrical/RMS Current Calculator. Function to evaluate the time-constant tau, the symmetrical fault current, and the RMS current for a faulted circuit. Parameters ---------- V: float Voltage magnitude at fault point, not described as line-to-line or line-to-neutral. R: float The fault resistance in ohms. X: float The fault impedance in ohms. t: float, optional The time in seconds. freq: float, optional The system frequency in Hz. Returns ------- tau: float The time-constant tau in seconds. Isym: float Symmetrical fault current in amps. Irms: float RMS fault current in amps. """ # Calculate Z and tau Z = _np.sqrt(R ** 2 + X ** 2) tau = X / (2 * _np.pi * freq * R) # Calculate Symmetrical Fault Current Isym = (V / _np.sqrt(3)) / Z # Calculate RMS Fault Current Irms = _np.sqrt(1 + 2 * _np.exp(-2 * t / tau)) * Isym return tau, Isym, Irms
# Define Relay M Formula
[docs] def faultratio(I, Ipickup, CTR=1): """ Fault Multiple of Pickup (Ratio) Calculator. Evaluates the CTR-scaled pickup measured to pickup current ratio. M = meas / pickup Parameters ---------- I: float Measured Current in Amps Ipickup: float Fault Current Pickup Setting (in Amps) CTR: float, optional Current Transformer Ratio for relay, default=1 Returns ------- M: float The measured-to-pickup ratio """ M = I / (CTR * Ipickup) return M
# Define Residual Compensation Factor Function
[docs] def residcomp(z1, z0, linelength=1): """ Residual Compensation Factor Function. Evaluates the residual compensation factor based on the line's positive and zero sequence impedance characteristics. Parameters ---------- z1: complex The positive-sequence impedance characteristic of the line, specified in ohms-per-unit where the total line length (of same unit) is specified in *linelength* argument. z0: complex The zero-sequence impedance characteristic of the line, specified in ohms-per-unit where the total line length (of same unit) is specified in *linelength* argument. linelength: float, optional The length (in same base unit as impedance characteristics) of the line. default=1 Returns ------- k0: complex The residual compensation factor. """ # Evaluate Z1L and Z0L Z1L = z1 * linelength Z0L = z0 * linelength # Calculate Residual Compensation Factor (k0) k0 = (Z0L - Z1L) / (3 * Z1L) return k0
# Define Relay Measured Impedance Functon for Distance Elements
[docs] def distmeasz(VLNmeas, If, Ip, Ipp, CTR=1, VTR=1, k0=None, z1=None, z0=None, linelength=1): """ Distance Element Measured Impedance Function. Function to evaluate the Relay-Measured-Impedance as calculated from the measured voltage, current, and line parameters. Parameters ---------- VLNmeas: complex Measured Line-to-Neutral voltage for the faulted phase in primary volts. If: complex Faulted phase current measured in primary amps. Ip: complex Secondary phase current measured in primary amps. Ipp: complex Terchiary phase current measured in primary amps. CTR: float, optional Current transformer ratio, default=1 VTR: float, optional Voltage transformer ratio, default=1 k0: complex, optional Residual Compensation Factor z1: complex, optional The positive-sequence impedance characteristic of the line, specified in ohms-per-unit where the total line length (of same unit) is specified in *linelength* argument. z0: complex, optional The zero-sequence impedance characteristic of the line, specified in ohms-per-unit where the total line length (of same unit) is specified in *linelength* argument. linelength: float, optional The length (in same base unit as impedance characteristics) of the line. default=1 Returns ------- Zmeas: complex The "measured" impedance as calculated by the relay. """ # Validate Residual Compensation Inputs if k0 == z1 == z0 is None: raise ValueError("Residual compensation arguments must be set.") if k0 is None and (z1 is None or z0 is None): raise ValueError("Both *z1* and *z0* must be specified.") # Calculate Residual Compensation if Necessary if k0 is None: k0 = residcomp(z1, z0, linelength) # Convert Primary Units to Secondary V = VLNmeas / VTR Ir = (If + Ip + Ipp) / CTR I = If / CTR # Calculate Measured Impedance Zmeas = V / (I + k0 * Ir) return Zmeas
# Define Transformer Tap Mismatch Function
[docs] def transmismatch(I1, I2, tap1, tap2): """ Electrical Transformer TAP Mismatch Function. Function to evaluate the transformer ratio mismatch for protection. Parameters ---------- I1: complex Current (in amps) on transformer primary side. I2: complex Current (in amps) on transformer secondary. tap1: float Relay TAP setting on the primary side. tap2: float Relay TAP setting on the secondary side. Returns ------- mismatch: float Transformer CT mismatch value associated with relay. """ # Evaluate MR MR = min(abs(I1 / I2), abs(tap1 / tap2)) # Calculate Mismatch mismatch = (abs(I1 / I2) - abs(tap1 / tap2)) * 100 / MR return mismatch
# Define High-Impedance Bus Protection Pickup Function
[docs] def highzvpickup(I, RL, Rct, CTR=1, threephase=False, Ks=1.5, Vstd=400, Kd=0.5): """ High Impedance Pickup Setting Function. Evaluates the voltage pickup setting for a high impedance bus protection system. Parameters ---------- I: float Fault current on primary side (in amps) RL: float One-way line resistance in ohms Rct: float Current Transformer Resistance in ohms CTR: float, optional Current Transformer Ratio, default=1 threephase: bool, optional Control argument to set the function to evaluate the result for a three-phase fault or unbalanced fault. default=False Ks: float, optional Security Factor for secure voltage pickup setting, default=1.5 Vstd: float, optional C-Class Voltage rating (i.e. C-400), default=400 Kd: float, optional The dependability factor for dependable voltage pickup setting, default=0.5 Returns ------- Vsens: float The calculated sensetive voltage-pickup. Vdep: float The calculated dependable voltage-pickup. """ # Condition Based on threephase Argument n = 2 if threephase: n = 1 # Evaluate Secure Voltage Pickup Vsens = Ks * (n * RL + Rct) * I / CTR # Evaluate Dependible Voltage Pickup Vdep = Kd * Vstd return Vsens, Vdep
# Define Minimum Current Pickup for High-Impedance Bus Protection
[docs] def highzmini(N, Ie, Irly=None, Vset=None, Rrly=2000, Imov=0, CTR=1): """ Minimum Current for High Impedance Protection Calculator. Evaluates the minimum pickup current required to cause high-impedance bus protection element pickup. Parameters ---------- N: int Number of Current Transformers included in scheme Ie: float The excitation current at the voltage setting Irly: float, optional The relay current at voltage setting Vset: float, optional The relay's voltage pickup setting in volts. Rrly: float, optional The relay's internal resistance in ohms, default=2000 Imov: float, optional The overvoltage protection current at the voltage setting. default=0.0 CTR: float, optional Current Transformer Ratio, default=1 Returns ------- Imin: float Minimum current required to cause high-impedance bus protection element pickup. """ # Validate Inputs if Irly == Vset is None: raise ValueError("Relay Current Required.") # Condition Inputs Ie = abs(Ie) Imov = abs(Imov) if Irly is None: Vset = abs(Vset) Irly = Vset / Rrly else: Irly = abs(Irly) # Evaluate Minimum Current Pickup Imin = (N * Ie + Irly + Imov) * CTR return (Imin)
# Define Instantaneous Overcurrent Pickup Formula
[docs] def instoc(Imin, CTR=1, Ki=0.5): """ Instantaneous OverCurrent Pickup Calculator. Using a sensetivity factor and the CTR, evaluates the secondary-level pickup setting for an instantaneous overcurrent element. Parameters ---------- Imin: float The minimum fault current in primary amps. CTR: float, optional Current Transformer Ratio, default=1 Ki: Sensetivity factor, default=0.5 Returns ------- Ipu: float The pickup setting for the instantaneous overcurrent element as referred to the secondary side. """ # Evaluate Overcurrent Pickup Setting Ipu = Ki * abs(Imin) / CTR return Ipu
# Define Generator Loss of Field Element Function
[docs] def genlossfield(Xd, Xpd, Zbase=1, CTR=1, VTR=1): """ Electric Generator Loss of Field Function. Generates the Loss-of-Field Element settings for a generator using the Xd value and per-unit base information. Parameters ---------- Xd: float The Transient Reactance (Xd) term. May be specified in ohms or Per-Unit ohms if *Zbase* is set. Xpd: float The Sub-Transient Reactance (X'd) term. May be specified in ohms or Per-Unit ohms if *Zbase* is set. Zbase: float, optional Base impedance, used to convert per-unit Xd and Xpd to secondary values. default=1 CTR: float, optional Current Transformer Ratio, default=1 VTR: float, optional Voltage Transformer Ratio, default=1 Returns ------- ZoneOff: float Zone Offset in ohms. Z1dia: float Zone 1 diameter in ohms. Z2dia: float Zone 2 diameter in ohms. """ # Condition Inputs Xd = abs(Xd) Xpd = abs(Xpd) Zbase = abs(Zbase) # Evaluate Xd_sec and Xpd_sec Xd_sec = Xd * Zbase * (CTR / VTR) Xpd_sec = Xd * Zbase * (CTR / VTR) # Determine Zone Offset ZoneOff = Xpd_sec / 2 # Evaluate Z1 Diameter and Z2 Diameter Z1dia = Zbase * CTR / VTR Z2dia = Xd_sec # Return return ZoneOff, Z1dia, Z2dia
# Define Thermal Time Limit Calculator
[docs] def thermaltime(In, Ibase, tbase): r""" Thermal Time Limit Calculator. Computes the maximum allowable time for a specified current `In` given parameters for a maximum current and time at some other level, (`Ibase`, `tbase`). Uses the following formula: .. math:: t_n=\frac{I_{base}^2*t_{base}}{I_n^2} Parameters ---------- In: float Current at which to calculate max time. Ibase: float Base current, at which maximum time `tbase` is allowable. tbase: float Base time for which a maximum allowable current `Ibase` is specified. Unitless. Returns ------- tn: float Time allowable for specified current, `In`. """ # Perform Calculation tn = (Ibase ** 2 * tbase) / (In ** 2) return tn
# Define Synch. Machine Fault Current Calculator
[docs] def synmach_Isym(t, Eq, Xd, Xdp, Xdpp, Tdp, Tdpp): r""" Synch. Machine Symmetrical Fault Current Calc. Determines the Symmetrical Fault Current of a synchronous machine given the machine parameters, the internal voltage, and the time for which to calculate. .. math:: I_a(t)=\sqrt{2}\left|E_q\right|\left[ \frac{1}{X_d}+\left(\frac{1}{X'_d}-\frac{1}{X_d} \right)\cdot e^{\frac{-t}{T'_d}}+\left(\frac{1} {X"_d}-\frac{1}{X'_d}\right)\cdot e^{\frac{-t}{T"_d}} \right] Parameters ---------- t: float Time at which to calculate the fault current Eq: float The internal machine voltage in per-unit-volts Xd: float The Xd (d-axis) reactance in per-unit-ohms Xdp: float The X"d (d-axis transient) reactance in per-unit-ohms Xdpp: float The X"d (d-axis subtransient) reactance in per-unit-ohms Tdp: float The T'd (d-axis transient) time constant of the machine in seconds Tdpp: float The T"d (d-axis subtransient) time constant of the machine in seconds Returns ------- Ia: float Peak symmetrical fault current in per-unit-amps """ # Calculate Time-Constant Term t_c = ( 1 / Xd + (1 / Xdp - 1 / Xd) * _np.exp(-t / Tdp) + (1 / Xdpp - 1 / Xdp) * _np.exp(-t / Tdpp) ) # Calculate Fault Current Ia = _np.sqrt(2) * abs(Eq) * t_c return Ia
# Define Synch. Machine Asymmetrical Current Calculator
[docs] def synmach_Iasym(t, Eq, Xdpp, Xqpp, Ta): r""" Synch. Machine Asymmetrical Fault Current Calc. Determines the asymmetrical fault current of a synchronous machine given the machine parameters, the internal voltage, and the time for which to calculate. .. math:: I_{asym}=\sqrt{2}\left|E_q\right|\frac{1}{2} \left(\frac{1}{X"_d}+\frac{1}{X"_q}\right)e^{\frac{-t} {T_a}} Parameters ---------- t: float Time at which to calculate the fault current Eq: float The internal machine voltage in per-unit-volts Xdpp: float The X"d (d-axis subtransient) reactance in per-unit-ohms Xqpp: float The X"q (q-axis subtransient) reactance in per-unit-ohms Ta: float Armature short-circuit (DC) time constant in seconds Returns ------- Iasym: float Peak asymmetrical fault current in per-unit-amps """ # Calculate Time Constant Term t_c = 1 / Xdpp + 1 / Xqpp # Calculate Asymmetrical Current Iasym = _np.sqrt(2) * abs(Eq) * 1 / 2 * t_c * _np.exp(-t / Ta) return Iasym
# Define Induction Machine Eigenvalue Calculator
[docs] def indmacheigenvalues(Lr, Ls, Lm, Rr, Rs, wrf=0, freq=60): """ Induction Machine Eigenvalue Calculator. Calculates the pertinent eigenvalues for an unloaded induction machine given a specific set of machine parameters. Parameters ---------- Lr: float Inductance of the Rotor (in Henrys). Ls: float Inductance of the Stator (in Henrys). Lm: float Inductance of the Magnetizing branch (in Henrys). Rr: float Resistance of the Rotor (in Ohms). Rs: float Resistance of the Stator (in Ohms). wrf: float, optional Frequency (in radians/sec) of the rotor slip. default=0 freq: float, optional Base frequency of the system (in Hertz). default=60 Returns ------- lam1: complex The First Eigenvalue lam2: complex The Second Eigenvalue """ # Calculate Required Values omega_e_base = 2 * _np.pi * freq omega_rf = wrf torque_s = Ls / (omega_e_base * Rs) torque_r = Lr / (omega_e_base * Rr) alpha = torque_r / torque_s phi = 1 - Lm ** 2 / (Ls * Lr) omega_r = omega_e_base # Calculate k1 k1 = -1 / (2 * phi * torque_r) * (1 + alpha) k1 += 1j * (omega_r / 2 - omega_rf) # Calculate k2 k2 = 1 / (2 * phi * torque_r) k2 *= _np.sqrt( (1 + alpha) ** 2 - 4 * phi * alpha - (omega_r * phi * torque_r) ** 2 + 2j * (alpha - 1) * omega_r * phi * torque_r ) # Evaluate Eigenvalues and Return lam1 = k1 + k2 lam2 = k1 - k2 return lam1, lam2
# Define IM 3-Phase SC Current Calculator
[docs] def indmachphs3sc(t, Is0, Lr, Ls, Lm, Rr, Rs, wrf=0, freq=60, real=True): """ Induction Machine 3-Phase SC Calculator. Determines the short-circuit current at a specified time for a three-phase fault on an unloaded induction machine. Parameters ---------- t: array_like The time at which to find the current, may be int, float, or numpy array. Is0: complex The initial (t=0) current on the stator. Lr: float Inductance of the Rotor (in Henrys). Ls: float Inductance of the Stator (in Henrys). Lm: float Inductance of the Magnetizing branch (in Henrys). Rr: float Resistance of the Rotor (in Ohms). Rs: float Resistance of the Stator (in Ohms). wrf: float, optional Frequency (in radians/sec) of the rotor slip. default=0 freq: float, optional Base frequency of the system (in Hertz). default=60 real: bool, optional Control argument to force returned value to be real part only. default=True Returns ------- ias: array_like Fault Current """ # Calculate Required Values omega_r = 2 * _np.pi * freq torque_s = Ls / (omega_r * Rs) phi = 1 - Lm ** 2 / (Ls * Lr) # Calculate Eigenvalues lam1, lam2 = indmacheigenvalues(Lr, Ls, Lm, Rr, Rs, wrf, freq) # Calculate pIs0 pIs0 = -(1 / (phi * torque_s) + 1j * (1 - phi) / phi * omega_r) * Is0 # Calculate Constants C1 = (lam2 * Is0 - pIs0) / (lam2 - lam1) C2 = (pIs0 - lam1 * Is0) / (lam2 - lam1) # Calculate ias and Return ias = C1 * _np.exp(lam1 * t) + C2 * _np.exp(lam2 * t) if real: ias = _np.real(ias) return ias
# Define IM Torque Calculation
[docs] def indmachphs3torq(t, Is0, Lr, Ls, Lm, Rr, Rs, wrf=0, freq=60): """ Induction Machine 3-Phase Torque Calculator. Determines the torque exerted during a three-phase fault on an induction machine. Parameters ---------- t: array_like The time at which to find the current, may be int, float, or numpy array. Is0: complex The initial (t=0) current on the stator. Lr: float Inductance of the Rotor (in Henrys). Ls: float Inductance of the Stator (in Henrys). Lm: float Inductance of the Magnetizing branch (in Henrys). Rr: float Resistance of the Rotor (in Ohms). Rs: float Resistance of the Stator (in Ohms). p: int Number of electrical poles. wrf: float, optional Frequency (in radians/sec) of the rotor slip. default=0 freq: float, optional Base frequency of the system (in Hertz). default=60 Returns ------- Tem: array_like Induction machine torque in N*m """ # Calculate Required Values omega_r = 2 * _np.pi * freq torque_s = Ls / (omega_r * Rs) phi = 1 - Lm ** 2 / (Ls * Lr) # Calculate Eigenvalues lam1, lam2 = indmacheigenvalues(Lr, Ls, Lm, Rr, Rs, wrf, freq) # Calculate pIs0 pIs0 = -(1 / (phi * torque_s) + 1j * (1 - phi) / phi * omega_r) * Is0 # Calculate Constants C1 = (lam2 * Is0 - pIs0) / (lam2 - lam1) C2 = (pIs0 - lam1 * Is0) / (lam2 - lam1) # Calculate ias and Return idqs = C1 * _np.exp(lam1 * t) + C2 * _np.exp(lam2 * t) idqr = C2 * _np.exp(lam1 * t) + C1 * _np.exp(lam2 * t) # Calculate Lambda lamdqr = Lm * idqs + Lr * idqr # Calculate Torque Tem = Lm / Lr * (lamdqr.real * idqs.imag - lamdqr.imag * idqs.real) return Tem
# Define Complete Sync. Mach. Fault Current Function
[docs] def synmach_ifault(t, Ea, alpha, Xd, Xdp, Xdpp, Xqpp, Tdp, Tdpp, Ta, freq=60): # noqa: D401 "Synchronous" is intentional descriptor """ Synchronous Machine Fault Current Calculator. Given machine parameters, fault inception angle, and time at which to calculate fault current, this function will identify the complete (symmetrical, asymmetrical, and double frequency) fault current. .. image:: /static/synmach_ifault_formula.png Parameters ---------- t: float Time at which to calculate the fault current Eq: float The internal machine voltage in per-unit-volts alpha: float Fault inception angle (in degrees) Xd: float The Xd (d-axis) reactance in per-unit-ohms Xdp: float The X"d (d-axis transient) reactance in per-unit-ohms Xdpp: float The X"d (d-axis sub-transient) reactance in per-unit-ohms Xqpp: float The X"q (q-axis sub-transient) reactance in per-unit-ohms Tdp: float The T'd (d-axis transient) time constant of the machine in seconds Tdpp: float The T"d (d-axis sub-transient) time constant of the machine in seconds Ta: float Armature short-circuit (DC) time constant in seconds freq: float, optional System (electrical) frequency (in degrees), default=60 Returns ------- ias: float Synchronous machine fault current (symmetrical, asymmetrical, and double frequency component) in amps """ # Calculate we Component we = 2 * _np.pi * freq # Condition Inputs Ea = abs(Ea) alpha = _np.radians(alpha) # Define Constant Term const = _np.sqrt(2) * Ea if Xqpp != 0: val = 1 / Xqpp else: val = 0 asym = 1 / 2 * (1 / Xdpp + val) * _np.exp(t / Ta) # Define Symmetrical Portion isym = ( const * (1 / Xd + (1 / Xdp - 1 / Xd) * _np.exp(-t / Tdp) + (1 / Xdpp - 1 / Xdp) * _np.exp(-t / Tdpp)) * _np.sin(we * t + alpha) ) # Define Asymmetrical Portion iasym = const * asym * _np.sin(alpha) # Define Double Frequency Term idbl = const * 1 / 2 * asym * _np.sin(2 * we * t + alpha) # Compose Complete Current Value ias = isym - iasym - idbl return ias