Electrical Power Engineering Faults Calculations.
>>> from electricpy import fault
"""
################################################################################
import numpy as _np
import matplotlib.pyplot as _plt
from scipy.optimize import fsolve as _fsolve
from electricpy.constants import *
from electricpy.conversions import seq_to_abc
def _phaseroll(M012, reference):
# Compute Dot Product
return seq_to_abc(M012, reference)
# Define Single Line to Ground Fault Function
[docs]
def single_phase_to_ground_fault(Vth, Zseq, Rf=0, sequence=True, reference='A'):
r"""
Single-Phase-to-Ground Fault Calculator.
This function will evaluate the Zero, Positive, and Negative
sequence currents for a single-line-to-ground fault.
.. math:: I_1 = \frac{V_{th}}{Z_0+Z_1+Z_2+3*R_f}
.. math:: I_2 = I_1
.. math:: I_0 = I_1
Parameters
----------
Vth: complex
The Thevenin-Equivalent-Voltage
Zseq: list of complex
Tupple of sequence reactances as (Z0, Z1, Z2)
Rf: complex, optional
The fault resistance, default=0
sequence: bool, optional
Control argument to force return into symmetrical-
or phase-domain values.
reference: {'A', 'B', 'C'}
Single character denoting the reference,
default='A'
Returns
-------
Ifault: list of complex,
The Array of Fault Currents as (If0, If1, If2)
"""
# Decompose Reactance Tuple
X0, X1, X2 = Zseq
# Ensure that X-components are imaginary
if not isinstance(X0, complex):
X0 *= 1j
if not isinstance(X1, complex):
X1 *= 1j
if not isinstance(X2, complex):
X2 *= 1j
# Calculate Fault Current
Ifault = Vth / (X0 + X1 + X2 + 3 * Rf)
Ifault = _np.array([Ifault, Ifault, Ifault])
# Prepare Value for return
if not sequence:
Ifault = _phaseroll(Ifault, reference) # Convert to ABC-Domain
# Return Value
return Ifault
# Alias Original Name
phs1g = single_phase_to_ground_fault
# Define Double Line to Ground Fault Current Calculator
[docs]
def double_phase_to_ground_fault(Vth, Zseq, Rf=0, sequence=True, reference='A'):
r"""
Double-Line-to-Ground Fault Calculator.
This function will evaluate the Zero, Positive, and Negative
sequence currents for a double-line-to-ground fault.
.. math:: I_1 = \frac{V_{th}}{Z_1+\frac{Z_2*(Z_0+3*R_f)}{Z_0+Z_2+3*R_f}}
.. math:: I_2 = -\frac{V_{th}-Z_1*I_1}{X_2}
.. math:: I_0 = -\frac{V_{th}-Z_1*I_1}{X_0+3*R_f}
Parameters
----------
Vth: complex
The Thevenin-Equivalent-Voltage
Zseq: list of complex
Tupple of sequence reactances as (Z0, Z1, Z2)
Rf: complex, optional
The fault resistance, default=0
sequence: bool, optional
Control argument to force return into symmetrical-
or phase-domain values.
reference: {'A', 'B', 'C'}
Single character denoting the reference,
default='A'
Returns
-------
Ifault: list of complex,
The Array of Fault Currents as (If0, If1, If2)
"""
# Decompose Reactance Tuple
X0, X1, X2 = Zseq
# Ensure that X-components are imaginary
if not isinstance(X0, complex):
X0 *= 1j
if not isinstance(X1, complex):
X1 *= 1j
if not isinstance(X2, complex):
X2 *= 1j
# Calculate Fault Currents
If1 = Vth / (X1 + (X2 * (X0 + 3 * Rf)) / (X0 + X2 + 3 * Rf))
If2 = -(Vth - X1 * If1) / X2
If0 = -(Vth - X1 * If1) / (X0 + 3 * Rf)
Ifault = _np.array([If0, If1, If2])
# Return Currents
if not sequence:
Ifault = _phaseroll(Ifault, reference) # Convert to ABC-Domain
return Ifault
# Alias Original Name
phs2g = double_phase_to_ground_fault
# Define Phase-to-Phase Fault Current Calculator
[docs]
def phase_to_phase_fault(Vth, Zseq, Rf=0, sequence=True, reference='A'):
r"""
Line-to-Line Fault Calculator.
This function will evaluate the Zero, Positive, and Negative
sequence currents for a phase-to-phase fault.
.. math:: I_1 = \frac{V_{th}}{Z_1+Z_2+R_f}
.. math:: I_2 = -I_1
.. math:: I_0 = 0
Parameters
----------
Vth: complex
The Thevenin-Equivalent-Voltage
Zseq: list of complex
Tupple of sequence reactances as (Z0, Z1, Z2)
Rf: complex, optional
The fault resistance, default=0
sequence: bool, optional
Control argument to force return into symmetrical-
or phase-domain values.
reference: {'A', 'B', 'C'}
Single character denoting the reference,
default='A'
Returns
-------
Ifault: list of complex,
The Array of Fault Currents as (If0, If1, If2)
"""
# Decompose Reactance Tuple
X0, X1, X2 = Zseq
# Ensure that X-components are imaginary
if not isinstance(X0, complex):
X0 *= 1j
if not isinstance(X1, complex):
X1 *= 1j
if not isinstance(X2, complex):
X2 *= 1j
# Calculate Fault Currents
If0 = 0
If1 = Vth / (X1 + X2 + Rf)
If2 = -If1
Ifault = _np.array([If0, If1, If2])
# Return Currents
if not sequence:
Ifault = _phaseroll(Ifault, reference) # Convert to ABC-Domain
return Ifault
# Alias Original Name
phs2 = phase_to_phase_fault
# Define Three-Phase Fault Current Calculator
[docs]
def three_phase_fault(Vth, Zseq, Rf=0, sequence=True, reference='A'):
r"""
Three-Phase Fault Calculator.
This function will evaluate the Zero, Positive, and Negative
sequence currents for a three-phase fault.
.. math:: I_1 = \frac{V_{th}}{Z_1+R_1}
.. math:: I_2 = 0
.. math:: I_0 = 0
Parameters
----------
Vth: complex
The Thevenin-Equivalent-Voltage
Zseq: list of complex
Tupple of sequence reactances as (Z0, Z1, Z2)
Rf: complex, optional
The fault resistance, default=0
sequence: bool, optional
Control argument to force return into symmetrical-
or phase-domain values.
reference: {'A', 'B', 'C'}
Single character denoting the reference,
default='A'
Returns
-------
Ifault: list of complex
The Fault Current, equal for 0, pos., and neg. seq.
"""
# Decompose Reactance Tuple
X0, X1, X2 = Zseq
# Ensure that X-components are imaginary
if not isinstance(X1, complex):
X1 *= 1j
# Calculate Fault Currents
Ifault = Vth / (X1 + Rf)
Ifault = _np.array([0, Ifault, 0])
# Prepare to Return Value
if not sequence:
Ifault = _phaseroll(Ifault, reference) # Convert to ABC-Domain
return Ifault
# Alias Original Name
phs3 = three_phase_fault
# Define Single Pole Open Calculator
[docs]
def poleopen1(Vth, Zseq, sequence=True, reference='A'):
r"""
Single Pole Open Fault Calculator.
This function will evaluate the Zero, Positive, and Negative
sequence currents for a single pole open fault.
.. math:: I_1 = \frac{V_{th}}{Z_1+(\frac{1}{Z_2}+\frac{1}{Z_0})^-1}
.. math:: I_2 = -I_1 * \frac{Z_0}{Z_2+Z_0}
.. math:: I_0 = -I_1 * \frac{Z_2}{Z_2+Z_0}
Parameters
----------
Vth: complex
The Thevenin-Equivalent-Voltage
Zseq: list of complex
Tupple of sequence reactances as (Z0, Z1, Z2)
sequence: bool, optional
Control argument to force return into symmetrical-
or phase-domain values.
reference: {'A', 'B', 'C'}
Single character denoting the reference, or the
faulted phase indicator; default='A'
Returns
-------
Ifault: list of complex,
The Array of Fault Currents as (If0, If1, If2)
"""
# Decompose Reactance Tuple
X0, X1, X2 = Zseq
# Ensure that X-components are imaginary
if not isinstance(X0, complex):
X0 *= 1j
if not isinstance(X1, complex):
X1 *= 1j
if not isinstance(X2, complex):
X2 *= 1j
# Calculate Fault Currents
If1 = Vth / (X1 + (1 / X2 + 1 / X0) ** (-1))
If2 = -If1 * X0 / (X2 + X0)
If0 = -If1 * X2 / (X2 + X0)
Ifault = _np.array([If0, If1, If2])
# Return Currents
if not sequence:
Ifault = _phaseroll(Ifault, reference) # Convert to ABC-Domain
return Ifault
# Define Double Pole Open Calculator
[docs]
def poleopen2(Vth, Zseq, sequence=True, reference='A'):
r"""
Single Pole Open Fault Calculator.
This function will evaluate the Zero, Positive, and Negative
sequence currents for a single pole open fault.
.. math:: I_1 = \frac{V_{th}}{Z_1+Z_2+Z_0}
.. math:: I_2 = I_1
.. math:: I_0 = I_1
Parameters
----------
Vth: complex
The Thevenin-Equivalent-Voltage
Zseq: list of complex
Tupple of sequence reactances as (Z0, Z1, Z2)
sequence: bool, optional
Control argument to force return into symmetrical-
or phase-domain values.
reference: {'A', 'B', 'C'}
Single character denoting the reference, or the
faulted phase indicator; default='A'
Returns
-------
Ifault: list of complex,
The Array of Fault Currents as (If0, If1, If2)
"""
# Decompose Reactance Tuple
X0, X1, X2 = Zseq
# Ensure that X-components are imaginary
if not isinstance(X0, complex):
X0 *= 1j
if not isinstance(X1, complex):
X1 *= 1j
if not isinstance(X2, complex):
X2 *= 1j
# Calculate Fault Currents
If1 = Vth / (X1 + X2 + X0)
If2 = If1
If0 = If1
Ifault = _np.array([If0, If1, If2])
# Return Currents
if not sequence:
Ifault = _phaseroll(Ifault, reference) # Convert to ABC-Domain
return Ifault
# Define MVA Short Circuit
[docs]
def short_circuit_mva(Zth=None, Isc=None, Vth=1):
r"""
Short-Circuit MVA Calculator.
Function defines a method of interpretively
calculating the short-circuit MVA value
given two of the three arguments. The formulas
are all based around the following:
.. math:: MVA_{sc} = V_{th}*I_{sc}
.. math:: V_{th} = I_{sc}*Z_{th}
Parameters
----------
Zth: float
The Thevenin-Equivalent-Impedance
Isc: float, optional
Short-Circuit-Current, if left as
None, will force function to use
default setting for Vth.
default=None
Vth: float, optional
The Thevenin-Equivalent-Voltage,
defaults to a 1-per-unit value.
default=1
Returns
-------
MVA: float
Short-Circuit MVA, not described
as three-phase or otherwise, such
determination is dependent upon
inputs.
"""
# Test for too few inputs
if not any((Zth, Isc)):
raise ValueError("Either Zth or Isc must be specified.")
# Condition Inputs
if Zth is not None:
Zth = abs(Zth)
if Isc is not None:
Isc = abs(Isc)
if Vth != 1:
Vth = abs(Vth)
# Calculate MVA from one of the available methods
if all((Zth, Isc)):
MVA = Isc ** 2 * Zth
elif all((Zth, Vth)):
MVA = Vth ** 2 / Zth
else:
MVA = Vth * Isc
# Return Value
return MVA
# Alias Original Name
scMVA = short_circuit_mva
# Define Explicitly 3-Phase MVAsc Calculator
[docs]
def phs3mvasc(Vth, Zseq, Rf=0, Sbase=1):
r"""
Three-Phase MVA Short-Circuit Calculator.
Calculator to evaluate the Short-Circuit MVA of a three-phase fault given the system
parameters of Vth, Zseq, and an optional Rf. Uses the formula as follows:
.. math:: MVA_{sc} = \frac{\left|V_{th}^2\right|}{|Z_1|} * Sbase
Parameters
----------
Vth: complex
The Thevenin-Equivalent-Voltage
Zseq: list of complex
Tupple of sequence reactances as (Z0, Z1, Z2)
Rf: complex, optional
The fault resistance, default=0
Sbase: real, optional
The per-unit base for power. default=1
Returns
-------
MVA: real
Three-Phase Short-Circuit MVA.
"""
# Calculate Three-Phase MVA
MVA = abs(Vth) ** 2 / abs(Zseq[1]) * Sbase
# Scale VA to MVA if Sbase is not 1
if Sbase != 1:
MVA = MVA * 1e-6 # Divide by 1e6 (M)
# Return
return MVA
# Define Explicitly 1-Phase MVAsc Calculator
[docs]
def phs1mvasc(Vth, Zseq, Rf=0, Sbase=1):
r"""
Single-Phase MVA Short-Circuit Calculator.
Calculator to evaluate the Short-Circuit MVA of a single-phase fault given the system
parameters of Vth, Zseq, and an optional Rf. Uses the formula as follows:
.. math:: MVA_{sc} = \left|I_1^2\right|*|Z_1| * Sbase
where:
.. math:: I_1 = \frac{V_{th}}{Z_0+Z_1+Z_2+3*R_f}
Parameters
----------
Vth: complex
The Thevenin-Equivalent-Voltage
Zseq: list of complex
Tupple of sequence reactances as (Z0, Z1, Z2)
Rf: complex, optional
The fault resistance, default=0
Sbase: real, optional
The per-unit base for power. default=1
Returns
-------
MVA: real
Single-Phase Short-Circuit MVA.
"""
# Decompose Reactance Tuple
X0, X1, X2 = Zseq
# Ensure that X-components are imaginary
if not isinstance(X0, complex):
X0 *= 1j
if not isinstance(X1, complex):
X1 *= 1j
if not isinstance(X2, complex):
X2 *= 1j
# Calculate Fault Current
Ifault = Vth / (X0 + X1 + X2 + 3 * Rf)
# Calculate MVA
MVA = abs(Ifault) ** 2 * abs(X1) * Sbase
# Scale VA to MVA if Sbase is not 1
if Sbase != 1:
MVA = MVA * 1e-6 # Divide by 1e6 (M)
# Return
return MVA
# Define Faulted Bus Voltage Calculator
[docs]
def busvolt(k, n, Vpf, Z0, Z1, Z2, If, sequence=True, reference='A'):
"""
Faulted Bus Voltage Calculator.
This function is designed to calculate the bus voltage(s)
given a specific set of fault characteristics.
Parameters
----------
k: float
Bus index at which to calculate faulted voltage
n: float
Bus index at which fault occurred
Vpf: complex
Voltage Pre-Fault, Singular Number
Z0: ndarray
Zero-Sequence Impedance Matrix
Z1: ndarray
Positive-Sequence Impedance Matrix
Z2: ndarray
Negative-Sequence Impedance Matrix
If: complex
Sequence Fault Current Evaluated at Bus *n*
sequence: bool, optional
Control argument to force return into symmetrical-
or phase-domain values.
reference: {'A', 'B', 'C'}
Single character denoting the reference,
default='A'
Returns
-------
Vf: complex
The Fault Voltage, set of sequence or phase voltages as
specified by *sequence*
"""
# Condition Inputs
k = k - 1
n = n - 1
Z0 = _np.asarray(Z0)
Z1 = _np.asarray(Z1)
Z2 = _np.asarray(Z2)
If = _np.asarray(If)
# Generate Arrays For Calculation
Vfmat = _np.array([0, Vpf, 0]).T
Zmat = _np.array([[Z0[k, n], 0, 0],
[0, Z1[k, n], 0],
[0, 0, Z2[k, n]]])
# Perform Calculation
Vf = Vfmat - Zmat.dot(If)
if not sequence:
Vf = _phaseroll(Vf, reference) # Convert to ABC-Domain
return Vf
# Define CT Saturation Function
[docs]
def ct_saturation(XoR, Imag, Vrated, Irated, CTR, Rb, Xb, remnance=0, freq=60,
ALF=20):
r"""
Electrical Current Transformer Saturation Calculator.
A function to determine the saturation value and a boolean indicator
showing whether or not CT is -in fact- saturated.
To perform this evaluation, we must satisfy the equation:
.. math::
20\geq(1+\frac{X}{R})*\frac{|I_{mag}|}{I_{rated}*CTR}
*\frac{\left|R_{burden}+j*\omega*\frac{X_{burden}}
{\omega}\right|*100}{V_{rated}*(1-remnanc)}
Parameters
----------
XoR: float
The X-over-R ratio of the system.
Imag: float
The (maximum) current magnitude to use for calculation,
typically the fault current.
Vrated: float
The rated voltage (accompanying the C-Class value) of
the CT.
Irated: float
The rated secondary current for the CT.
CTR: float
The CT Ratio (primary/secondary, N) to be used.
Rb: float
The total burden resistance in ohms.
Xb: float
The total burden reactance in ohms.
remnance: float, optional
The system flux remnance, default=0.
freq: float, optional
The system frequency in Hz, default=60.
ALF: float, optional
The Saturation Constant which must be satisfied,
default=20.
Returns
-------
result: float
The calculated Saturation value.
saturation: bool
Boolean indicator to mark presence of saturation.
"""
# Define omega
w = 2 * _np.pi * freq
# Find Lb
Lb = Xb / w
# Re-evaluate Vrated
Vrated = Vrated * (1 - remnance)
# Calculate each "term" (multiple)
t1 = (1 + XoR)
t2 = (Imag / (Irated * CTR))
t3 = abs(Rb + 1j * w * Lb) * 100 / Vrated
# Evaluate
result = t1 * t2 * t3
# Test for saturation
saturation = result >= ALF
# Return Results
return result, saturation
# Define C-Class Calculator
[docs]
def ct_cclass(XoR, Imag, Irated, CTR, Rb, Xb, remnance=0, sat_crit=20):
r"""
Electrical Current Transformer (CT) C-Class Function.
A function to determine the C-Class rated voltage for a CT.
The formula shown below demonstrates the standard formula
which is normally used to evaluate the saturation criteria.
Worth noting here, is the fact that :math:`V_{rated}` is the
CT C-Class.
.. math::
\text{Saturation Criteria}=\frac{(1+\frac{X}{R})\cdot
\frac{|I_{mag}|}{I_{rated}\cdot CTR}\cdot\frac{\left|
R_{burden}+j\cdot X_{burden}\right|\cdot100}{V_{rated}}}
{1-remnance}
For the purposes of this function, the above formula is applied
as follows to evaluate the CT C-Class such as to satisfy the
saturation criteria defined.
.. math::
\text{CT C-Class}=\frac{(1+\frac{X}{R})\cdot
\frac{|I_{mag}|}{I_{rated}\cdot CTR}\cdot\frac{
\left|R_{burden}+j\cdot X_{burden}\right|\cdot100}
{\text{Saturation Criteria (i.e., 20)}}}{1-remnance}
Parameters
----------
XoR: float
The X-over-R ratio of the system.
Imag: float
The (maximum) current magnitude to use for calculation,
typically the fault current.
Irated: float
The rated secondary current for the CT.
CTR: float
The CT Ratio (primary/secondary, N) to be used.
Rb: float
The total burden resistance in ohms.
Xb: float
The total burden reactance in ohms.
remnance: float, optional
The system flux remnance, default=0.
sat_crit: float, optional
The saturation criteria which must be satisfied,
typically such that CT saturation will not occur,
default=20.
Returns
-------
c_class: float
The calculated C-Class rated voltage.
"""
# Calculate each "term" (multiple)
t1 = (1 + XoR)
t2 = (Imag / (Irated * CTR))
t3 = abs(Rb + 1j * Xb) * 100 / sat_crit
# Evaluate
Vr_w_rem = t1 * t2 * t3
c_class = Vr_w_rem / (1 - remnance)
# Return Result
return c_class
# Define Saturation Voltage at Rated Burden
[docs]
def ct_satratburden(Inom, VArat=None, ANSIv=None, ALF=20, ):
r"""
Electrical Current Transformer (CT) Saturation at Rated Burden Calculator.
A function to determine the Saturation at rated burden.
.. math:: V_{saturated}=ALF*\frac{VA_{rated}}{I_{nominal}}
where:
.. math:: VA_{rated}=I_{nominal}*\frac{ANSI_{voltage}}{20}
Parameters
----------
Inom: float
Nominal Current
VArat: float, optional, exclusive
The apparent power (VA) rating of the CT.
ANSIv: float, optional, exclusive
The ANSI voltage requirement to meet.
ALF: float, optional
Accuracy Limit Factor, default=20.
Returns
-------
Vsat: float
The saturated voltage.
"""
# Validate Inputs
if VArat is None and ANSIv is None:
raise ValueError("VArat or ANSIv must be specified.")
elif VArat is None:
# Calculate VArat from ANSIv
VArat = Inom * ANSIv / (20)
# Determine Vsaturation
Vsat = ALF * VArat / Inom
return Vsat
# Define CT Vpeak Formula
[docs]
def ct_vpeak(Zb, Ip, CTR):
r"""
Electrical Current Transformer (CT) Peak Voltage Calculator.
Simple formula to calculate the Peak Voltage of a CT.
.. math:: \sqrt{3.5*|Z_burden|*I_{peak}*CTR}
Parameters
----------
Zb: float
The burden impedance magnitude (in ohms).
Ip: float
The peak current for the CT.
CTR: float
The CTR turns ratio of the CT.
Returns
-------
Vpeak: float
The peak voltage.
"""
return _np.sqrt(3.5 * abs(Zb) * Ip * CTR)
# Define Saturation Time Calculator
[docs]
def ct_timetosat(Vknee, XoR, Rb, CTR, Imax, ts=None, npts=100, freq=60,
plot=False):
r"""
Electrical Current Transformer (CT) Time to Saturation Function.
Function to determine the "time to saturate" for an underrated C-Class
CT using three standard curves described by Juergen Holbach.
Parameters
----------
Vknee: float
The knee-voltage for the CT.
XoR: float
The X-over-R ratio of the system.
Rb: float
The total burden resistance in ohms.
CTR: float
The CT Ratio (primary/secondary, N) to be used.
Imax: float
The (maximum) current magnitude to use for calculation,
typically the fault current.
ts: numpy.ndarray or float, optional
The time-array or particular (floatint point) time at which
to calculate the values. default=_np.linspace(0,0.1,freq*npts)
npts: float, optional
The number of points (per cycle) to calculate if ts is not
specified, default=100.
freq: float, optional
The system frequency in Hz, default=60.
plot: bool, optional
Control argument to enable plotting of calculated curves,
default=False.
"""
# Calculate omega
w = 2 * _np.pi * freq
# Calculate Tp
Tp = XoR / w
# If ts isn't specified, generate it
if ts is None:
ts = _np.linspace(0, 0.1, freq * npts)
# Calculate inner term
term = -XoR * (_np.exp(-ts / Tp) - 1)
# Calculate Vsaturation terms
Vsat1 = Imax * Rb * (term + 1)
Vsat2 = Imax * Rb * (term - _np.sin(w * ts))
Vsat3 = Imax * Rb * (1 - _np.cos(w * ts))
# If plotting requested
if plot and isinstance(ts, _np.ndarray):
_plt.plot(ts, Vsat1, label="Vsat1")
_plt.plot(ts, Vsat2, label="Vsat2")
_plt.plot(ts, Vsat3, label="Vsat3")
_plt.axhline(Vknee, label="V-knee", linestyle='--')
_plt.title("Saturation Curves")
_plt.xlabel("Time (ts)")
_plt.legend()
_plt.show()
elif plot:
print("Unable to plot a single point, *ts* must be a numpy-array.")
# Determine the crossover points for each saturation curve
Vsat1c = Vsat2c = Vsat3c = 0
if isinstance(ts, _np.ndarray):
for i in range(len(ts)):
if Vsat1[i] > Vknee and Vsat1c == 0:
Vsat1c = ts[i - 1]
if Vsat2[i] > Vknee and Vsat2c == 0:
Vsat2c = ts[i - 1]
if Vsat3[i] > Vknee and Vsat3c == 0:
Vsat3c = ts[i - 1]
results = (Vsat1c, Vsat2c, Vsat3c)
else:
results = (Vsat1, Vsat2, Vsat3)
return results
# Define Function to Calculate TRV
[docs]
def pktransrecvolt(C, L, R=0, VLL=None, VLN=None, freq=60):
"""
Peak Transient Recovery Function.
Peak Transient Recovery Voltage calculation function, evaluates the peak
transient recovery voltage (restriking voltage) and the
Rate-of-Rise-Recovery Voltage.
Parameters
----------
C: float
Capacitance Value in Farads.
L: float
Inductance in Henries.
R: float, optional
The resistance of the system used for
calculation, default=0.
VLL: float, exclusive
Line-to-Line voltage, exclusive
optional argument.
VLN: float, exclusive
Line-to-Neutral voltage, exclusive
optional argument.
freq: float, optional
System frequency in Hz.
Returns
-------
Vcpk: float
Peak Transient Recovery Voltage in volts.
RRRV: float
The RRRV (Rate-of-Rise-Recovery Voltage)
calculated given the parameters in volts
per second.
"""
# Evaluate alpha, omega-n, and fn
alpha = R / (2 * L)
wn = 1 / _np.sqrt(L * C) - alpha
fn = wn / (2 * _np.pi)
# Evaluate Vm
if VLL is not None:
Vm = _np.sqrt(2 / 3) * VLL
elif VLN is not None:
Vm = _np.sqrt(2) * VLN
else:
raise ValueError("One voltage must be specified.")
# Evaluate Vcpk (worst case)
Vcpk = wn ** 2 / (wn ** 2 - 2 * _np.pi * freq) * Vm * 2
# Evaluate RRRV
RRRV = 2 * Vm * fn / 0.5
return Vcpk, RRRV
# Define TRV Reduction Resistor Function
[docs]
def trvresistor(C, L, reduction, Rd0=500, wd0=260e3, tpk0=10e-6):
"""
Transient Recovery Voltage (TRV) Reduction Resistor Function.
Function to find the resistor value that will reduce the TRV by a specified
percentage.
Parameters
----------
C: float
Capacitance Value in Farads.
L: float
Inductance in Henries.
reduction: float
The percentage that the TRV should be reduced by.
Rd0: float, optional
Damping Resistor Evaluation Starting Point, default=500
wd0: float, optional
Omega-d evaluation starting point, default=260*k
tpk0: float, optional
Time of peak voltage evaluation starting point, default=10*u
Returns
-------
Rd: float
Damping resistor value, in ohms.
wd: float
Omega-d
tpk: float
Time of peak voltage.
"""
# Evaluate omega-n
wn = 1 / _np.sqrt(L * C)
# Generate Constant Factor
fctr = (1 - reduction) * 2 - 1
# Define Function Set
def equations(data):
Rd, wd, tpk = data
X = _np.sqrt(wn ** 2 - (1 / (2 * Rd * C)) ** 2) - wd
Y = _np.exp(-tpk / (2 * Rd * C)) - fctr
Z = wd * tpk - _np.pi
return (X, Y, Z)
Rd, wd, tpk = _fsolve(equations, (Rd0, wd0, tpk0))
return Rd, wd, tpk
# Define Time-Overcurrent Trip Time Function
[docs]
def toctriptime(I, Ipickup, TD, curve="U1", CTR=1):
"""
Time OverCurrent Trip Time Function.
Time-OverCurrent Trip Time Calculator, evaluates the time
to trip for a specific TOC (51) element given the curve
type, current characteristics and time-dial setting.
Parameters
----------
I: float
Measured Current in Amps
Ipickup: float
Fault Current Pickup Setting (in Amps)
TD: float
Time Dial Setting
curve: string, optional
Name of specified TOC curve, may be entry from set:
{U1,U2,U3,U4,U5,C1,C2,C3,C4,C5}, default=U1
CTR: float, optional
Current Transformer Ratio, default=1
Returns
-------
tt: float
Time-to-Trip for characterized element.
"""
# Condition Inputs
curve = curve.upper()
# Define Dictionary of Constants
const = {"U1": {"A": 0.0104, "B": 0.2256, "P": 0.02},
"U2": {"A": 5.95, "B": 0.180, "P": 2.00},
"U3": {"A": 3.88, "B": 0.0963, "P": 2.00},
"U4": {"A": 5.67, "B": 0.352, "P": 2.00},
"U5": {"A": 0.00342, "B": 0.00262, "P": 0.02},
"C1": {"A": 0.14, "B": 0, "P": 0.02},
"C2": {"A": 13.5, "B": 0, "P": 2.00},
"C3": {"A": 80.0, "B": 0, "P": 2.00},
"C4": {"A": 120.0, "B": 0, "P": 2.00},
"C5": {"A": 0.05, "B": 0, "P": 0.04}}
# Load Constants
A = const[curve]["A"]
B = const[curve]["B"]
P = const[curve]["P"]
# Evaluate M
M = I / (CTR * Ipickup)
# Evaluate Trip Time
tt = TD * (A / (M ** P - 1) + B)
return tt
# Define Time Overcurrent Reset Time Function
[docs]
def tocreset(I, Ipickup, TD, curve="U1", CTR=1):
"""
Time OverCurrent Reset Time Function.
Function to calculate the time to reset for a TOC
(Time-OverCurrent, 51) element.
Parameters
----------
I: float
Measured Current in Amps
Ipickup: float
Fault Current Pickup Setting (in Amps)
TD: float
Time Dial Setting
curve: string, optional
Name of specified TOC curve, may be entry from set:
{U1,U2,U3,U4,U5,C1,C2,C3,C4,C5}, default=U1
CTR: float, optional
Current Transformer Ratio, default=1
Returns
-------
tr: float
Time-to-Reset for characterized element.
"""
# Condition Inputs
curve = curve.upper()
# Define Dictionary of Constants
C = {"U1": 1.08, "U2": 5.95, "U3": 3.88,
"U4": 5.67, "U5": 0.323, "C1": 13.5,
"C2": 47.3, "C3": 80.0, "C4": 120.0,
"C5": 4.85}
# Evaluate M
M = I / (CTR * Ipickup)
# Evaluate Reset Time
tr = TD * (C[curve] / (1 - M ** 2))
return tr
# Define Pickup Current Calculation
[docs]
def pickup(Iloadmax, Ifaultmin, scale=0, printout=False, units="A"):
"""
Electrical Current Pickup Selection Assistant.
Used to assist in evaluating an optimal phase-over-current pickup
setting. Uses maximum load and minimum fault current to provide
user assistance.
Parameters
----------
Iloadmax: float
The maximum load current in amps.
Ifaultmin: float
The minimum fault current in amps.
scale: int, optional
Control scaling to set number of significant figures.
default=0
printout: boolean, optional
Control argument to enable printing of intermediate
stages, default=False.
units: string, optional
String to be appended to any printed output denoting
the units of which are being printed, default="A"
Returns
-------
setpoint: float
The evaluated setpoint at which the function suggests
the phase-over-current pickup setting be placed.
"""
IL2 = 2 * Iloadmax
IF2 = Ifaultmin / 2
exponent = len(str(IL2).split('.')[0])
setpoint = _np.ceil(IL2 * 10 ** (-exponent + 1 + scale)) * 10 ** (exponent - 1 - scale)
if printout:
print("Range Min:", IL2, units, "\t\tRange Max:", IF2, units)
if IF2 < setpoint:
setpoint = IL2
if IL2 > IF2:
raise ValueError("Invalid Parameters.")
if printout:
print("Current Pickup:", setpoint, units)
return setpoint
# Define Time-Dial Coordination Function
[docs]
def tdradial(I, CTI, Ipu_up, Ipu_dn=0, TDdn=0, curve="U1", scale=2, freq=60,
CTR_up=1, CTR_dn=1, tfixed=None):
"""
Radial Time Dial Coordination Function.
Function to evaluate the Time-Dial (TD) setting in radial schemes
where the Coordinating Time Interval (CTI) and the up/downstream
pickup settings are known along with the TD setting for the
downstream protection.
Parameters
----------
I: float
Measured fault current in Amps, typically set using the
maximum fault current available.
CTI: float
Coordinating Time Interval in cycles.
Ipu_up: float
Pickup setting for upstream protection,
specified in amps
Ipu_dn: float, optional
Pickup setting for downstream protection,
specified in amps, default=0
TDdn: float, optional
Time-Dial setting for downstream protection,
specified in seconds, default=0
curve: string, optional
Name of specified TOC curve, may be entry from set:
{U1,U2,U3,U4,U5,C1,C2,C3,C4,C5}, default=U1
scale: int, optional
Scaling value used to evaluate a practical TD
setting, default=2
freq: float, optional
System operating frequency, default=60
CTR_up: float, optional
Current Transformer Ratio for upstream relay.
default=1
CTR_dn: float, optional
Current Transformer Ratio for downstream relay.
default=1
tfixed: float, optional
Used to specify a fixed time delay for coordinated
protection elements, primarily used for coordinating
TOC elements (51) with OC elements (50) with a fixed
tripping time. Overrides downstream TOC arguments
including *Ipu_dn* and *TDdn*.
Returns
-------
TD: float
Calculated Time-Dial setting according to radial
scheme logical analysis.
"""
# Condition Inputs
curve = curve.upper()
# Define Dictionary of Constants
const = {"U1": {"A": 0.0104, "B": 0.2256, "P": 0.02},
"U2": {"A": 5.95, "B": 0.180, "P": 2.00},
"U3": {"A": 3.88, "B": 0.0963, "P": 2.00},
"U4": {"A": 5.67, "B": 0.352, "P": 2.00},
"U5": {"A": 0.00342, "B": 0.00262, "P": 0.02},
"C1": {"A": 0.14, "B": 0, "P": 0.02},
"C2": {"A": 13.5, "B": 0, "P": 2.00},
"C3": {"A": 80.0, "B": 0, "P": 2.00},
"C4": {"A": 120.0, "B": 0, "P": 2.00},
"C5": {"A": 0.05, "B": 0, "P": 0.04}}
# Load Constants
A = const[curve]["A"]
B = const[curve]["B"]
P = const[curve]["P"]
if tfixed is None:
# Evaluate in seconds from cycles
CTI = CTI / freq
# Evaluate M
M = I / (CTR_dn * Ipu_dn)
# Evaluate Trip Time
tpu_desired = TDdn * (A / (M ** P - 1) + B) + CTI
else:
tpu_desired = tfixed + CTI
# Re-Evaluate M
M = I / (CTR_up * Ipu_up)
# Calculate TD setting
TD = tpu_desired / (A / (M ** 2 - 1) + B)
# Scale and Round
TD = _np.floor(TD * 10 ** scale) / 10 ** scale
return TD
# Define TAP Calculator
[docs]
def protectiontap(S, CTR=1, VLN=None, VLL=None):
"""
Protection TAP Setting Calculator.
Evaluates the required TAP setting based on the rated power of
a transformer (the object being protected) and the voltage
(either primary or secondary) in conjunction with the CTR
(current transformer ratio) for the side in question (primary/
secondary).
Parameters
----------
CTR: float
The Current Transformer Ratio.
S: float
Rated apparent power magnitude (VA/VAR/W).
VLN: float, exclusive
Line-to-Neutral voltage in volts.
VLL: float, exclusive
Line-to-Line voltage in volts.
Returns
-------
TAP: float
The TAP setting required to meet the specifications.
"""
# Condition Voltage(s)
if VLL is not None:
V = abs(_np.sqrt(3) * VLL)
elif VLN is not None:
V = abs(3 * VLN)
else:
raise ValueError("One or more voltages must be provided.")
# Calculate TAP
TAP = abs(S) / (V * CTR)
return TAP
# Define Current Correction Calculator
[docs]
def correctedcurrents(Ipri, TAP, correction="Y", CTR=1):
"""
Electrical Transformer Current Correction Function.
Function to evaluate the currents as corrected for microprocessor-
based relay protection schemes.
Parameters
----------
Ipri: list of complex
Three-phase set (IA, IB, IC) of primary currents.
TAP: float
Relay's TAP setting.
correction: string, optional
String defining correction factor, may be one of:
(Y, D+, D-, Z); Y denotes Y (Y0) connection, D+
denotes Dab (D1) connection, D- denotes Dac (D11)
connection, and Z (Z12) denotes zero-sequence
removal. default="Y"
CTR: float
Current Transformer Ratio, default=1
Returns
-------
Isec_corr: list of complex
The corrected currents to perform operate/restraint
calculations with.
"""
# Define Matrix Lookup
MAT = {"Y": XFMY0,
"D+": XFMD1,
"D-": XFMD11,
"Z": XFM12}
# Condition Inputs
Ipri = _np.asarray(Ipri)
if isinstance(correction, list):
mult = MAT[correction[0]]
for i in correction[1:]:
mult = mult.dot(MAT[i])
elif isinstance(correction, str):
mult = MAT[correction]
elif isinstance(correction, _np.ndarray):
mult = correction
else:
raise ValueError("Correction must be string or list of strings.")
# Evaluate Corrected Current
Isec_corr = 1 / TAP * mult.dot(Ipri / CTR)
return Isec_corr
# Define Iop/Irt Calculator
[docs]
def iopirt(IpriHV, IpriLV, TAPHV, TAPLV, corrHV="Y", corrLV="Y", CTRHV=1,
CTRLV=1):
"""
Operate/Restraint Current Calculator.
Calculates the operating current (Iop) and the restraint
current (Irt) as well as the slope.
Parameters
----------
IpriHV: list of complex
Three-phase set (IA, IB, IC) of primary currents
on the high-voltage side of power transformer.
IpriLV list of complex
Three-phase set (IA, IB, IC) of primary currents
on the low-voltage side of power transformer.
TAPHV float
Relay's TAP setting for high-voltage side of
power transformer.
TAPLV float
Relay's TAP setting for low-voltage side of
power transformer.
corrHV string, optional
String defining correction factor on high-voltage
side of power transformer, may be one of:
(Y, D+, D-, Z); Y denotes Y (Y0) connection, D+
denotes Dab (D1) connection, D- denotes Dac (D11)
connection, and Z (Z12) denotes zero-sequence
removal. default="Y"
corrLV string, optional
String defining correction factor on low-voltage
side of power transformer, may be one of:
(Y, D+, D-, Z); Y denotes Y (Y0) connection, D+
denotes Dab (D1) connection, D- denotes Dac (D11)
connection, and Z (Z12) denotes zero-sequence
removal. default="Y"
CTRHV float
Current Transformer Ratio for high-voltage side
of power transformer, default=1
CTRLV float
Current Transformer Ratio for low-voltage side
of power transformer, default=1
Returns
-------
Iop: list of float
The operating currents for phases A, B, and C.
Irt: list of float
The restraint currents for phases A, B, and C.
slope: list of float
The calculated slopes for phases A, B, and C.
"""
# Calculate Corrected Currents
IcorHV = correctedcurrents(IpriHV, TAPHV, corrHV, CTRHV)
IcorLV = correctedcurrents(IpriLV, TAPLV, corrLV, CTRLV)
# Calculate Operate/Restraint Currents
Iop = _np.absolute(IcorHV + IcorLV)
Irt = _np.absolute(IcorHV) + _np.absolute(IcorLV)
# Calculate Slopes
slope = Iop / Irt
return Iop, Irt, slope
# Define Symmetrical/RMS Current Calculation
[docs]
def symrmsfaultcur(V, R, X, t=1 / 60, freq=60):
"""
Symmetrical/RMS Current Calculator.
Function to evaluate the time-constant tau, the symmetrical fault current,
and the RMS current for a faulted circuit.
Parameters
----------
V: float
Voltage magnitude at fault point,
not described as line-to-line or
line-to-neutral.
R: float
The fault resistance in ohms.
X: float
The fault impedance in ohms.
t: float, optional
The time in seconds.
freq: float, optional
The system frequency in Hz.
Returns
-------
tau: float
The time-constant tau in seconds.
Isym: float
Symmetrical fault current in amps.
Irms: float
RMS fault current in amps.
"""
# Calculate Z and tau
Z = _np.sqrt(R ** 2 + X ** 2)
tau = X / (2 * _np.pi * freq * R)
# Calculate Symmetrical Fault Current
Isym = (V / _np.sqrt(3)) / Z
# Calculate RMS Fault Current
Irms = _np.sqrt(1 + 2 * _np.exp(-2 * t / tau)) * Isym
return tau, Isym, Irms
# Define Relay M Formula
[docs]
def faultratio(I, Ipickup, CTR=1):
"""
Fault Multiple of Pickup (Ratio) Calculator.
Evaluates the CTR-scaled pickup measured to pickup current ratio.
M = meas / pickup
Parameters
----------
I: float
Measured Current in Amps
Ipickup: float
Fault Current Pickup Setting (in Amps)
CTR: float, optional
Current Transformer Ratio for relay,
default=1
Returns
-------
M: float
The measured-to-pickup ratio
"""
M = I / (CTR * Ipickup)
return M
# Define Residual Compensation Factor Function
[docs]
def residcomp(z1, z0, linelength=1):
"""
Residual Compensation Factor Function.
Evaluates the residual compensation factor based on the line's positive and
zero sequence impedance characteristics.
Parameters
----------
z1: complex
The positive-sequence impedance
characteristic of the line, specified in
ohms-per-unit where the total line length
(of same unit) is specified in
*linelength* argument.
z0: complex
The zero-sequence impedance characteristic
of the line, specified in ohms-per-unit
where the total line length (of same unit)
is specified in *linelength* argument.
linelength: float, optional
The length (in same base unit as impedance
characteristics) of the line. default=1
Returns
-------
k0: complex
The residual compensation factor.
"""
# Evaluate Z1L and Z0L
Z1L = z1 * linelength
Z0L = z0 * linelength
# Calculate Residual Compensation Factor (k0)
k0 = (Z0L - Z1L) / (3 * Z1L)
return k0
# Define Relay Measured Impedance Functon for Distance Elements
[docs]
def distmeasz(VLNmeas, If, Ip, Ipp, CTR=1, VTR=1, k0=None, z1=None, z0=None,
linelength=1):
"""
Distance Element Measured Impedance Function.
Function to evaluate the Relay-Measured-Impedance as calculated from
the measured voltage, current, and line parameters.
Parameters
----------
VLNmeas: complex
Measured Line-to-Neutral voltage for the
faulted phase in primary volts.
If: complex
Faulted phase current measured in primary
amps.
Ip: complex
Secondary phase current measured in primary
amps.
Ipp: complex
Terchiary phase current measured in primary
amps.
CTR: float, optional
Current transformer ratio, default=1
VTR: float, optional
Voltage transformer ratio, default=1
k0: complex, optional
Residual Compensation Factor
z1: complex, optional
The positive-sequence impedance
characteristic of the line, specified in
ohms-per-unit where the total line length
(of same unit) is specified in
*linelength* argument.
z0: complex, optional
The zero-sequence impedance characteristic
of the line, specified in ohms-per-unit
where the total line length (of same unit)
is specified in *linelength* argument.
linelength: float, optional
The length (in same base unit as impedance
characteristics) of the line. default=1
Returns
-------
Zmeas: complex
The "measured" impedance as calculated by the relay.
"""
# Validate Residual Compensation Inputs
if k0 == z1 == z0 is None:
raise ValueError("Residual compensation arguments must be set.")
if k0 is None and (z1 is None or z0 is None):
raise ValueError("Both *z1* and *z0* must be specified.")
# Calculate Residual Compensation if Necessary
if k0 is None:
k0 = residcomp(z1, z0, linelength)
# Convert Primary Units to Secondary
V = VLNmeas / VTR
Ir = (If + Ip + Ipp) / CTR
I = If / CTR
# Calculate Measured Impedance
Zmeas = V / (I + k0 * Ir)
return Zmeas
# Define Transformer Tap Mismatch Function
[docs]
def transmismatch(I1, I2, tap1, tap2):
"""
Electrical Transformer TAP Mismatch Function.
Function to evaluate the transformer ratio mismatch for protection.
Parameters
----------
I1: complex
Current (in amps) on transformer primary side.
I2: complex
Current (in amps) on transformer secondary.
tap1: float
Relay TAP setting on the primary side.
tap2: float
Relay TAP setting on the secondary side.
Returns
-------
mismatch: float
Transformer CT mismatch value associated with
relay.
"""
# Evaluate MR
MR = min(abs(I1 / I2), abs(tap1 / tap2))
# Calculate Mismatch
mismatch = (abs(I1 / I2) - abs(tap1 / tap2)) * 100 / MR
return mismatch
# Define High-Impedance Bus Protection Pickup Function
[docs]
def highzvpickup(I, RL, Rct, CTR=1, threephase=False, Ks=1.5,
Vstd=400, Kd=0.5):
"""
High Impedance Pickup Setting Function.
Evaluates the voltage pickup setting for a high
impedance bus protection system.
Parameters
----------
I: float
Fault current on primary side (in amps)
RL: float
One-way line resistance in ohms
Rct: float
Current Transformer Resistance in ohms
CTR: float, optional
Current Transformer Ratio, default=1
threephase: bool, optional
Control argument to set the function to
evaluate the result for a three-phase
fault or unbalanced fault. default=False
Ks: float, optional
Security Factor for secure voltage pickup
setting, default=1.5
Vstd: float, optional
C-Class Voltage rating (i.e. C-400),
default=400
Kd: float, optional
The dependability factor for dependable
voltage pickup setting, default=0.5
Returns
-------
Vsens: float
The calculated sensetive voltage-pickup.
Vdep: float
The calculated dependable voltage-pickup.
"""
# Condition Based on threephase Argument
n = 2
if threephase: n = 1
# Evaluate Secure Voltage Pickup
Vsens = Ks * (n * RL + Rct) * I / CTR
# Evaluate Dependible Voltage Pickup
Vdep = Kd * Vstd
return Vsens, Vdep
# Define Minimum Current Pickup for High-Impedance Bus Protection
[docs]
def highzmini(N, Ie, Irly=None, Vset=None, Rrly=2000, Imov=0, CTR=1):
"""
Minimum Current for High Impedance Protection Calculator.
Evaluates the minimum pickup current required to cause
high-impedance bus protection element pickup.
Parameters
----------
N: int
Number of Current Transformers included in scheme
Ie: float
The excitation current at the voltage setting
Irly: float, optional
The relay current at voltage setting
Vset: float, optional
The relay's voltage pickup setting in volts.
Rrly: float, optional
The relay's internal resistance in ohms, default=2000
Imov: float, optional
The overvoltage protection current at the
voltage setting. default=0.0
CTR: float, optional
Current Transformer Ratio, default=1
Returns
-------
Imin: float
Minimum current required to cause high-impedance
bus protection element pickup.
"""
# Validate Inputs
if Irly == Vset is None:
raise ValueError("Relay Current Required.")
# Condition Inputs
Ie = abs(Ie)
Imov = abs(Imov)
if Irly is None:
Vset = abs(Vset)
Irly = Vset / Rrly
else:
Irly = abs(Irly)
# Evaluate Minimum Current Pickup
Imin = (N * Ie + Irly + Imov) * CTR
return (Imin)
# Define Instantaneous Overcurrent Pickup Formula
[docs]
def instoc(Imin, CTR=1, Ki=0.5):
"""
Instantaneous OverCurrent Pickup Calculator.
Using a sensetivity factor and the CTR, evaluates the secondary-level pickup
setting for an instantaneous overcurrent element.
Parameters
----------
Imin: float
The minimum fault current in primary amps.
CTR: float, optional
Current Transformer Ratio, default=1
Ki: Sensetivity factor, default=0.5
Returns
-------
Ipu: float
The pickup setting for the instantaneous
overcurrent element as referred to the
secondary side.
"""
# Evaluate Overcurrent Pickup Setting
Ipu = Ki * abs(Imin) / CTR
return Ipu
# Define Generator Loss of Field Element Function
[docs]
def genlossfield(Xd, Xpd, Zbase=1, CTR=1, VTR=1):
"""
Electric Generator Loss of Field Function.
Generates the Loss-of-Field Element settings for a generator using the Xd
value and per-unit base information.
Parameters
----------
Xd: float
The Transient Reactance (Xd) term. May be
specified in ohms or Per-Unit ohms if
*Zbase* is set.
Xpd: float
The Sub-Transient Reactance (X'd) term. May
be specified in ohms or Per-Unit ohms if
*Zbase* is set.
Zbase: float, optional
Base impedance, used to convert per-unit
Xd and Xpd to secondary values. default=1
CTR: float, optional
Current Transformer Ratio, default=1
VTR: float, optional
Voltage Transformer Ratio, default=1
Returns
-------
ZoneOff: float
Zone Offset in ohms.
Z1dia: float
Zone 1 diameter in ohms.
Z2dia: float
Zone 2 diameter in ohms.
"""
# Condition Inputs
Xd = abs(Xd)
Xpd = abs(Xpd)
Zbase = abs(Zbase)
# Evaluate Xd_sec and Xpd_sec
Xd_sec = Xd * Zbase * (CTR / VTR)
Xpd_sec = Xd * Zbase * (CTR / VTR)
# Determine Zone Offset
ZoneOff = Xpd_sec / 2
# Evaluate Z1 Diameter and Z2 Diameter
Z1dia = Zbase * CTR / VTR
Z2dia = Xd_sec
# Return
return ZoneOff, Z1dia, Z2dia
# Define Thermal Time Limit Calculator
[docs]
def thermaltime(In, Ibase, tbase):
r"""
Thermal Time Limit Calculator.
Computes the maximum allowable time for a specified current `In` given
parameters for a maximum current and time at some other level, (`Ibase`,
`tbase`).
Uses the following formula:
.. math:: t_n=\frac{I_{base}^2*t_{base}}{I_n^2}
Parameters
----------
In: float
Current at which to calculate max time.
Ibase: float
Base current, at which maximum time
`tbase` is allowable.
tbase: float
Base time for which a maximum allowable
current `Ibase` is specified. Unitless.
Returns
-------
tn: float
Time allowable for specified current,
`In`.
"""
# Perform Calculation
tn = (Ibase ** 2 * tbase) / (In ** 2)
return tn
# Define Synch. Machine Fault Current Calculator
[docs]
def synmach_Isym(t, Eq, Xd, Xdp, Xdpp, Tdp, Tdpp):
r"""
Synch. Machine Symmetrical Fault Current Calc.
Determines the Symmetrical Fault Current of a synchronous
machine given the machine parameters, the internal voltage,
and the time for which to calculate.
.. math:: I_a(t)=\sqrt{2}\left|E_q\right|\left[
\frac{1}{X_d}+\left(\frac{1}{X'_d}-\frac{1}{X_d}
\right)\cdot e^{\frac{-t}{T'_d}}+\left(\frac{1}
{X"_d}-\frac{1}{X'_d}\right)\cdot e^{\frac{-t}{T"_d}}
\right]
Parameters
----------
t: float
Time at which to calculate the fault current
Eq: float
The internal machine voltage in per-unit-volts
Xd: float
The Xd (d-axis) reactance in per-unit-ohms
Xdp: float
The X"d (d-axis transient) reactance in
per-unit-ohms
Xdpp: float
The X"d (d-axis subtransient) reactance in
per-unit-ohms
Tdp: float
The T'd (d-axis transient) time constant of the
machine in seconds
Tdpp: float
The T"d (d-axis subtransient) time constant of
the machine in seconds
Returns
-------
Ia: float
Peak symmetrical fault current in per-unit-amps
"""
# Calculate Time-Constant Term
t_c = (
1 / Xd +
(1 / Xdp - 1 / Xd) * _np.exp(-t / Tdp) +
(1 / Xdpp - 1 / Xdp) * _np.exp(-t / Tdpp)
)
# Calculate Fault Current
Ia = _np.sqrt(2) * abs(Eq) * t_c
return Ia
# Define Synch. Machine Asymmetrical Current Calculator
[docs]
def synmach_Iasym(t, Eq, Xdpp, Xqpp, Ta):
r"""
Synch. Machine Asymmetrical Fault Current Calc.
Determines the asymmetrical fault current of a synchronous
machine given the machine parameters, the internal voltage,
and the time for which to calculate.
.. math:: I_{asym}=\sqrt{2}\left|E_q\right|\frac{1}{2}
\left(\frac{1}{X"_d}+\frac{1}{X"_q}\right)e^{\frac{-t}
{T_a}}
Parameters
----------
t: float
Time at which to calculate the fault current
Eq: float
The internal machine voltage in per-unit-volts
Xdpp: float
The X"d (d-axis subtransient) reactance in
per-unit-ohms
Xqpp: float
The X"q (q-axis subtransient) reactance in
per-unit-ohms
Ta: float
Armature short-circuit (DC) time constant in seconds
Returns
-------
Iasym: float
Peak asymmetrical fault current in per-unit-amps
"""
# Calculate Time Constant Term
t_c = 1 / Xdpp + 1 / Xqpp
# Calculate Asymmetrical Current
Iasym = _np.sqrt(2) * abs(Eq) * 1 / 2 * t_c * _np.exp(-t / Ta)
return Iasym
# Define Induction Machine Eigenvalue Calculator
[docs]
def indmacheigenvalues(Lr, Ls, Lm, Rr, Rs, wrf=0, freq=60):
"""
Induction Machine Eigenvalue Calculator.
Calculates the pertinent eigenvalues for an unloaded
induction machine given a specific set of machine
parameters.
Parameters
----------
Lr: float
Inductance of the Rotor (in Henrys).
Ls: float
Inductance of the Stator (in Henrys).
Lm: float
Inductance of the Magnetizing branch
(in Henrys).
Rr: float
Resistance of the Rotor (in Ohms).
Rs: float
Resistance of the Stator (in Ohms).
wrf: float, optional
Frequency (in radians/sec) of the rotor slip.
default=0
freq: float, optional
Base frequency of the system (in Hertz).
default=60
Returns
-------
lam1: complex
The First Eigenvalue
lam2: complex
The Second Eigenvalue
"""
# Calculate Required Values
omega_e_base = 2 * _np.pi * freq
omega_rf = wrf
torque_s = Ls / (omega_e_base * Rs)
torque_r = Lr / (omega_e_base * Rr)
alpha = torque_r / torque_s
phi = 1 - Lm ** 2 / (Ls * Lr)
omega_r = omega_e_base
# Calculate k1
k1 = -1 / (2 * phi * torque_r) * (1 + alpha)
k1 += 1j * (omega_r / 2 - omega_rf)
# Calculate k2
k2 = 1 / (2 * phi * torque_r)
k2 *= _np.sqrt(
(1 + alpha) ** 2 - 4 * phi * alpha - (omega_r * phi * torque_r) ** 2 +
2j * (alpha - 1) * omega_r * phi * torque_r
)
# Evaluate Eigenvalues and Return
lam1 = k1 + k2
lam2 = k1 - k2
return lam1, lam2
# Define IM 3-Phase SC Current Calculator
[docs]
def indmachphs3sc(t, Is0, Lr, Ls, Lm, Rr, Rs, wrf=0, freq=60, real=True):
"""
Induction Machine 3-Phase SC Calculator.
Determines the short-circuit current at a specified time for a three-phase
fault on an unloaded induction machine.
Parameters
----------
t: array_like
The time at which to find the
current, may be int, float, or
numpy array.
Is0: complex
The initial (t=0) current on
the stator.
Lr: float
Inductance of the Rotor (in Henrys).
Ls: float
Inductance of the Stator (in Henrys).
Lm: float
Inductance of the Magnetizing branch
(in Henrys).
Rr: float
Resistance of the Rotor (in Ohms).
Rs: float
Resistance of the Stator (in Ohms).
wrf: float, optional
Frequency (in radians/sec) of the rotor slip.
default=0
freq: float, optional
Base frequency of the system (in Hertz).
default=60
real: bool, optional
Control argument to force returned value
to be real part only. default=True
Returns
-------
ias: array_like
Fault Current
"""
# Calculate Required Values
omega_r = 2 * _np.pi * freq
torque_s = Ls / (omega_r * Rs)
phi = 1 - Lm ** 2 / (Ls * Lr)
# Calculate Eigenvalues
lam1, lam2 = indmacheigenvalues(Lr, Ls, Lm, Rr, Rs, wrf, freq)
# Calculate pIs0
pIs0 = -(1 / (phi * torque_s) + 1j * (1 - phi) / phi * omega_r) * Is0
# Calculate Constants
C1 = (lam2 * Is0 - pIs0) / (lam2 - lam1)
C2 = (pIs0 - lam1 * Is0) / (lam2 - lam1)
# Calculate ias and Return
ias = C1 * _np.exp(lam1 * t) + C2 * _np.exp(lam2 * t)
if real:
ias = _np.real(ias)
return ias
# Define IM Torque Calculation
[docs]
def indmachphs3torq(t, Is0, Lr, Ls, Lm, Rr, Rs, wrf=0, freq=60):
"""
Induction Machine 3-Phase Torque Calculator.
Determines the torque exerted during a three-phase fault on an induction
machine.
Parameters
----------
t: array_like
The time at which to find the
current, may be int, float, or
numpy array.
Is0: complex
The initial (t=0) current on
the stator.
Lr: float
Inductance of the Rotor (in Henrys).
Ls: float
Inductance of the Stator (in Henrys).
Lm: float
Inductance of the Magnetizing branch
(in Henrys).
Rr: float
Resistance of the Rotor (in Ohms).
Rs: float
Resistance of the Stator (in Ohms).
p: int
Number of electrical poles.
wrf: float, optional
Frequency (in radians/sec) of the rotor slip.
default=0
freq: float, optional
Base frequency of the system (in Hertz).
default=60
Returns
-------
Tem: array_like
Induction machine torque in N*m
"""
# Calculate Required Values
omega_r = 2 * _np.pi * freq
torque_s = Ls / (omega_r * Rs)
phi = 1 - Lm ** 2 / (Ls * Lr)
# Calculate Eigenvalues
lam1, lam2 = indmacheigenvalues(Lr, Ls, Lm, Rr, Rs, wrf, freq)
# Calculate pIs0
pIs0 = -(1 / (phi * torque_s) + 1j * (1 - phi) / phi * omega_r) * Is0
# Calculate Constants
C1 = (lam2 * Is0 - pIs0) / (lam2 - lam1)
C2 = (pIs0 - lam1 * Is0) / (lam2 - lam1)
# Calculate ias and Return
idqs = C1 * _np.exp(lam1 * t) + C2 * _np.exp(lam2 * t)
idqr = C2 * _np.exp(lam1 * t) + C1 * _np.exp(lam2 * t)
# Calculate Lambda
lamdqr = Lm * idqs + Lr * idqr
# Calculate Torque
Tem = Lm / Lr * (lamdqr.real * idqs.imag - lamdqr.imag * idqs.real)
return Tem
# Define Complete Sync. Mach. Fault Current Function
[docs]
def synmach_ifault(t, Ea, alpha, Xd, Xdp, Xdpp, Xqpp, Tdp, Tdpp, Ta, freq=60):
# noqa: D401 "Synchronous" is intentional descriptor
"""
Synchronous Machine Fault Current Calculator.
Given machine parameters, fault inception angle, and time at
which to calculate fault current, this function will identify
the complete (symmetrical, asymmetrical, and double frequency)
fault current.
.. image:: /static/synmach_ifault_formula.png
Parameters
----------
t: float
Time at which to calculate the fault current
Eq: float
The internal machine voltage in per-unit-volts
alpha: float
Fault inception angle (in degrees)
Xd: float
The Xd (d-axis) reactance in per-unit-ohms
Xdp: float
The X"d (d-axis transient) reactance in
per-unit-ohms
Xdpp: float
The X"d (d-axis sub-transient) reactance in
per-unit-ohms
Xqpp: float
The X"q (q-axis sub-transient) reactance in
per-unit-ohms
Tdp: float
The T'd (d-axis transient) time constant of the
machine in seconds
Tdpp: float
The T"d (d-axis sub-transient) time constant of
the machine in seconds
Ta: float
Armature short-circuit (DC) time constant in seconds
freq: float, optional
System (electrical) frequency (in degrees),
default=60
Returns
-------
ias: float
Synchronous machine fault current (symmetrical,
asymmetrical, and double frequency component) in
amps
"""
# Calculate we Component
we = 2 * _np.pi * freq
# Condition Inputs
Ea = abs(Ea)
alpha = _np.radians(alpha)
# Define Constant Term
const = _np.sqrt(2) * Ea
if Xqpp != 0:
val = 1 / Xqpp
else:
val = 0
asym = 1 / 2 * (1 / Xdpp + val) * _np.exp(t / Ta)
# Define Symmetrical Portion
isym = (
const * (1 / Xd + (1 / Xdp - 1 / Xd) * _np.exp(-t / Tdp) +
(1 / Xdpp - 1 / Xdp) * _np.exp(-t / Tdpp)) * _np.sin(we * t + alpha)
)
# Define Asymmetrical Portion
iasym = const * asym * _np.sin(alpha)
# Define Double Frequency Term
idbl = const * 1 / 2 * asym * _np.sin(2 * we * t + alpha)
# Compose Complete Current Value
ias = isym - iasym - idbl
return ias
# END