electricpy.fault.highzvpickup¶
-
electricpy.fault.highzvpickup(I, RL, Rct, CTR=
1
, threephase=False
, Ks=1.5
, Vstd=400
, Kd=0.5
)[source]¶ High Impedance Pickup Setting Function.
Evaluates the voltage pickup setting for a high impedance bus protection system.
- Parameters:¶
- I : float¶
Fault current on primary side (in amps)
- RL : float¶
One-way line resistance in ohms
- Rct : float¶
Current Transformer Resistance in ohms
- CTR : float, optional¶
Current Transformer Ratio, default=1
- threephase : bool, optional¶
Control argument to set the function to evaluate the result for a three-phase fault or unbalanced fault. default=False
- Ks : float, optional¶
Security Factor for secure voltage pickup setting, default=1.5
- Vstd : float, optional¶
C-Class Voltage rating (i.e. C-400), default=400
- Kd : float, optional¶
The dependability factor for dependable voltage pickup setting, default=0.5
- Returns:¶
Vsens (float) – The calculated sensetive voltage-pickup.
Vdep (float) – The calculated dependable voltage-pickup.