electricpy.fault.highzvpickup

electricpy.fault.highzvpickup(I, RL, Rct, CTR=1, threephase=False, Ks=1.5, Vstd=400, Kd=0.5)[source]

High Impedance Pickup Setting Function.

Evaluates the voltage pickup setting for a high impedance bus protection system.

Parameters:
I : float

Fault current on primary side (in amps)

RL : float

One-way line resistance in ohms

Rct : float

Current Transformer Resistance in ohms

CTR : float, optional

Current Transformer Ratio, default=1

threephase : bool, optional

Control argument to set the function to evaluate the result for a three-phase fault or unbalanced fault. default=False

Ks : float, optional

Security Factor for secure voltage pickup setting, default=1.5

Vstd : float, optional

C-Class Voltage rating (i.e. C-400), default=400

Kd : float, optional

The dependability factor for dependable voltage pickup setting, default=0.5

Returns:

  • Vsens (float) – The calculated sensetive voltage-pickup.

  • Vdep (float) – The calculated dependable voltage-pickup.