electricpy.fault.single_phase_to_ground_fault¶
-
electricpy.fault.single_phase_to_ground_fault(Vth, Zseq, Rf=
0
, sequence=True
, reference='A'
)[source]¶ Single-Phase-to-Ground Fault Calculator.
This function will evaluate the Zero, Positive, and Negative sequence currents for a single-line-to-ground fault.
\[I_1 = \frac{V_{th}}{Z_0+Z_1+Z_2+3*R_f}\]\[I_2 = I_1\]\[I_0 = I_1\]- Parameters:¶
- Vth : complex¶
The Thevenin-Equivalent-Voltage
- Zseq : list of complex¶
Tupple of sequence reactances as (Z0, Z1, Z2)
- Rf : complex, optional¶
The fault resistance, default=0
- sequence : bool, optional¶
Control argument to force return into symmetrical- or phase-domain values.
- reference : {'A', 'B', 'C'}¶
Single character denoting the reference, default=’A’
- Returns:¶
Ifault – The Array of Fault Currents as (If0, If1, If2)
- Return type:¶
list of complex,