electricpy.fault.correctedcurrents¶
-
electricpy.fault.correctedcurrents(Ipri, TAP, correction=
'Y'
, CTR=1
)[source]¶ Electrical Transformer Current Correction Function.
Function to evaluate the currents as corrected for microprocessor- based relay protection schemes.
- Parameters:¶
- Ipri : list of complex¶
Three-phase set (IA, IB, IC) of primary currents.
- TAP : float¶
Relay’s TAP setting.
- correction : string, optional¶
String defining correction factor, may be one of: (Y, D+, D-, Z); Y denotes Y (Y0) connection, D+ denotes Dab (D1) connection, D- denotes Dac (D11) connection, and Z (Z12) denotes zero-sequence removal. default=”Y”
- CTR : float¶
Current Transformer Ratio, default=1
- Returns:¶
Isec_corr – The corrected currents to perform operate/restraint calculations with.
- Return type:¶
list of complex